
34
Parameter setting
Sensor Sewi KNX TH-L-Pr
• Version: 17.11.2016 • Technical changes and errors excepted.
Define the
output type and value
. As a result of the different types, switchable lights
(1 bit), dimmer (1 Byte 0-100%), scenarios (1 Byte 0...63 scenario call-up) and other fun-
ctions can be controlled.
Select whether delays can be set via objects and specify the
switching delays
. By set-
ting a
blocking time
after switch-off, you prevent sensors from recognising a swit-
ched-off lamp in their detection zone as a temperature change, and sending a motion
message.
Set the master's output
sending pattern
.
In addition, you can refer to a
slave signal
, i.e. a signal from an additional motion de-
tector, for controlling purposes.
Output type
• 1 bit
• 1 byte (0...255)
• 1 byte (0%...100%)
• 1 byte (0°...360°)
• 1 byte (0...63) scenario call-up
• 2 byte counter without math. symbol
• 2 byte counter with math. symbol
• 2 byte floating point
• 4 byte counter without math. symbol
• 4 byte counter with math. symbol
• 4 byte floating point
Output value in the event of motion
e.g. 0 • 1 [depending on the output type]
Output value without motion
e.g. 0 • 1 [depending on the output type]
Output value when blocked
e.g. 0 • 1 [depending on the output type]
Delays can be set via objects
(in seconds)
No • Yes
Switch on delay
(for setting via objects: valid until
1st communication)
0 s • 5 s • 10 s • ... 2 h
(for daylight dependent motion detection:
fixed value 0s)
Switch off delay
(for setting via objects: valid until
1st communication)
0 s • 5 s • 10 s • ... 2 h
Blocking time for motion detection
after switch off delay in seconds
0...600 ; 2
Sending pattern
• on change
• on change to movement
• on change to no movement
• on change and periodically
• on change to movement and periodically
• on change to no movement periodically
Cycle
(if sent periodically)
1s • 5 s • ... 2 h
Use slave signal
No • Yes