54

Parameter setting

Sensor Sewi KNX TH-L-Pr

 • Version: 17.11.2016 • Technical changes and errors excepted.

When the 

threshold value per parameter

 is specified, then the value is set.

When the 

threshold value per communication object

 is specified, the starting

value, object value limit and type of change to the threshold value are then set.

With both of the methods for specifying the threshold values the hysteresis is set.

Switching output

Define which value the output transmits if the threshold value is exceeded or undercut.
Set the delay for the switching and in which cases the switch output transmits. 

Threshold value in kLux

1000 … 150000; 60000

Start threshold value in Lux
valid until first call

1000 … 150000; 60000

   Object value limit (min.) in Lux

1000 … 150000

   Object value limit (max.) in Lux

1000 … 150000

Type of threshold change

Absolute value • Increase/decrease

Increment in Lux

(upon increase/decrease change)

1000 • 2000 • 5000 • 10000 • 20000

Hysteresis setting

in % • absolute

Hysteresis in % of the threshold value

(for setting in %)

0 … 100; 50

Hysteresis in Lux

(for absolute setting)

0 … 150000; 30000

When the following conditions apply, the 
output is
(LV = Threshold value)

• GW above = 1 | GW - Hyst. below = 0 
• GW above = 0 | GW - Hyst. below = 1
• GW below = 1 | GW + Hyst. above = 0
• GW below = 0 | GW + Hyst. above = 1

Delays can be set via objects 
(in seconds)

No • Yes

Delay from 0 to 1 

none • 1 s … 2 h

Delay from 1 to 0

none  • 1 s … 2 h

Switching output sends

• on change 
• on change to 1 
• on change to 0 
• on change and periodically 
• on change to 1 and periodically
• on change to 0 and periodically

Cycle 

(if sent periodically)

5 s ... 2 h

Содержание Sewi KNX TH-L-Pr

Страница 1: ...Installation and Adjustment Item number 70398 EN Sewi KNXTH L Pr Combined Indoor Sensor...

Страница 2: ...tocol 15 5 1 List of all communication objects 15 6 Parameter setting 29 6 1 Behaviour on power failure restoration of power 29 6 2 General settings 30 6 3 Motion detector 30 6 3 1 Master 1 2 3 4 32 6...

Страница 3: ...ion 17 11 2016 Technical changes and errors excepted 6 17 Comfort field 65 6 18 Variable comparator 66 6 18 1 Control variable comparator 1 2 3 4 66 6 19 Computer 66 6 19 1 Computer 1 8 67 6 20 Logic...

Страница 4: ...eshooting of the device must only be carried out by a competent electrician Safety advice Safety advice for working on electrical connections components etc DANGER indicates an immediately hazardous s...

Страница 5: ...4 Clarification of signs...

Страница 6: ...t value and external value can be set as a percentage Bus message whether the values for temperature and air humidity are within the comfort field DIN 1946 Dew point calculation Switching outputs for...

Страница 7: ...tage KNX bus voltage Bus current max 10 mA Data output KNX bus plug in terminal BCU type Integrated microcontroller PEI type 0 Group addresses max 2000 Assignments max 2000 Communication objects 377 T...

Страница 8: ...ted live components inside the device National legal regulations are to be followed Ensure that all lines to be assembled are free of voltage and take precautions against accidental switching on Do no...

Страница 9: ...lease ensure that the measurement results of temperature and humidity are affected as little as possible by external influences Possible sources of interference include Direct sunlight Drafts from win...

Страница 10: ...or Sewi KNX TH L Pr Version 17 11 2016 Technical changes and errors excepted Size of the coverage area Distance Length Width 2 50 m approx 7 42 m approx 5 66 m 3 50 m approx 10 38 m approx 7 92 m Fig...

Страница 11: ...7 11 2016 Technical changes and errors excepted 2 3 Construction of the sensor 2 3 1 Housing from the outside 1 Fig 3 1 Brightness sensor 2 Motion sensor A Recess to open the housing When closing the...

Страница 12: ...ly Fig 4 1 Brightness sensor 2 Motion sensor 3 Sensors for temperature humidity 4 a b Long holes for mounting hole distance 60 mm 5 KNX terminal BUS 6 Programming LED 7 Programming button 8 Cable bush...

Страница 13: ...After the bus voltage has been applied the device will enter an initialisation phase last ing a few seconds During this phase no information can be received or sent via the bus The motion sensor has...

Страница 14: ...u can program a differ ent address in the ETS by overwriting the address 15 15 250 or by teaching the device via the programming button The programming button is on the inside of the housing Fig 4 No...

Страница 15: ...14 Maintenance Sensor Sewi KNX TH L Pr Version 17 11 2016 Technical changes and errors excepted...

Страница 16: ...ature sensor Measured value Output R CT 9 1 DPT_Val ue_Temp 2 bytes 44 Temperature sensor Total measurement Output R CT 9 1 DPT_Val ue_Temp 2 bytes 45 Temperature sensor Min Max measurement query Inpu...

Страница 17: ...old value 3 Switching delay from 0 to 1 Input WC 7 5 DPT_Time PeriodSec 2 bytes 68 Temp threshold value 3 Switching delay from 1 to 0 Input WC 7 5 DPT_Time PeriodSec 2 bytes 69 Temp threshold value 3...

Страница 18: ...ss sensor 2 threshold value 2 Switching output Output R CT 1 1 DPT_Switch 1 bit 141 Brightness sensor 2 threshold value 2 Switching output block Input WC 1 1 DPT_Switch 1 bit 143 Brightness sensor 2 t...

Страница 19: ...Minimum measurement Output R CT 9 7 DPT_Val ue_Humidity 2 bytes 319 Humidity sensor Maximum measurement Output R CT 9 7 DPT_Val ue_Humidity 2 bytes 320 Humidity sensor Min Max measurement reset Input...

Страница 20: ...eshold value 4 1 0 Input WC 1 1 DPT_Switch 1 bit 351 Humidity threshold value 4 Delay from 0 to 1 Input WC 7 5 DPT_Time PeriodSec 2 bytes 352 Humidity threshold value 4 Delay from 1 to 0 Input WC 7 5...

Страница 21: ...itch 1 bit 487 Temp controller Setpoint comfort heating Input Output RWCT 9 1 DPT_Val ue_Temp 2 bytes 488 Temp controller Setpoint comfort heating 1 0 Input WC 1 1 DPT_Switch 1 bit 489 Temp controller...

Страница 22: ...1 DPT_Switch 1 bit 508 Temp controller Status cooling level 2 1 ON 0 OFF Output R CT 1 1 DPT_Switch 1 bit 509 Temp controller Comfort extension status Input Output RWCT 1 1 DPT_Switch 1 bit 510 Temp c...

Страница 23: ...Output Output R CT 5 1 DPT_Scaling 1 byte 1117 Control variable comparator 1 Block block Output WC 1 2 DPT_Bool 1 bit 1118 Control variable comparator 2 Input 1 Input WC 5 1 DPT_Scaling 1 byte 1119 C...

Страница 24: ...41 Computer 1 Input I1 Input RWCT 4 bytes 1142 Computer 1 Input I2 Input RWCT 4 bytes 1143 Computer 1 Input I3 Input RWCT 4 bytes 1144 Computer 1 Output O1 Output R CT 4 bytes 1145 Computer 1 Output O...

Страница 25: ...mputer 5 Output O1 Output R CT 4 bytes 1177 Computer 5 Output O2 Output R CT 4 bytes 1178 Computer 5 Condition text Output R CT 16 0 DPT_String_ASCII 14 bytes 1179 Computer 5 Monitoring status Output...

Страница 26: ...2 DPT_Bool 1 bit 1400 Logic input 10 Input WC 1 2 DPT_Bool 1 bit 1401 Logic input 11 Input WC 1 2 DPT_Bool 1 bit 1402 Logic input 12 Input WC 1 2 DPT_Bool 1 bit 1403 Logic input 13 Input WC 1 2 DPT_B...

Страница 27: ...1 1 DPT_Switch 1 bit 1443 OR logic 1 1 bit switching output Output R CT 1 2 DPT_Bool 1 bit 1444 OR logic 1 8 bit output A Output R CT 1 byte 1445 OR logic 1 8 bit output B Output R CT 1 byte 1446 OR l...

Страница 28: ...r 1 Brightness threshold value on Input Output RWCT 9 4 DPT_Val ue_Lux 2 bytes 1532 Motion detector Master 1 Brightness threshold value off Input Output RWCT 9 4 DPT_Val ue_Lux 2 bytes 1533 Motion det...

Страница 29: ...4 bytes 1555 Motion detector Master 3 Switch on delay Input LSK 7 5 DPT_Time PeriodSec 2 bytes 1556 Motion detector Master 3 Switch off delay Input LSK 7 5 DPT_Time PeriodSec 2 bytes 1557 Motion detec...

Страница 30: ...DPT_Scaling 1 byte 1586 Light controller Target actual difference Input Output RWCT 9 4 DPT_Val ue_Lux 2 bytes 1587 Light controller Reset time Input Output RWCT 7 5 DPT_Time PeriodSec 2 bytes 1588 Li...

Страница 31: ...nd after a reset it takes 15 seconds until the sensor is ready for operation Activate the test object if you would like to test the motion detection while commis sioning With an active test object you...

Страница 32: ...set can be found in chapter Align communication between master and slave page 35 Set the sending cycle shorter than the master s switch off delay Set the object type and value for the cycle reset inpu...

Страница 33: ...detection can be used via separate threshold values for switch on and switch off or dependent on daylight The separate threshold values are ideal for controlling the light in rooms which are only illu...

Страница 34: ...the measured bright ness value If the room brightness later exceeds this total value because the room is illuminated by daylight the motion control is switched off Settings for all types of motion det...

Страница 35: ...io call up 2 byte counter without math symbol 2 byte counter with math symbol 2 byte floating point 4 byte counter without math symbol 4 byte counter with math symbol 4 byte floating point Output valu...

Страница 36: ...r than the master s switch off delay Thereby it is ensured that the master does not perform a switch off action while the slave is still de tecting a motion Slave cycle reset The cycle reset for the s...

Страница 37: ...TH L Pr detects the brightness in the room Activate the light control Set in which cases the data received via object for setpoint value setpoint value ac tual difference dimming increment and times...

Страница 38: ...output This results in the manual light operation having priority Regulation starts on movement reception of a start stop object reception of a start stop object or movement Regulation stops on moveme...

Страница 39: ...external value Set the mixed value calculation if desired If an external portion is used all of the following settings threshold values etc are related to the overall reading Use interruptions No Yes...

Страница 40: ...be used for the initial start up as the factory settings are always used until the first communication setting via objects is ignored Set the threshold value directly in the application program using...

Страница 41: ...ype of threshold value specification Switching output Set the behaviour of the switching output when a threshold value is exceeded under cut The output switching delay can be set using objects or dire...

Страница 42: ...2 h Use switching output block No Yes Analysis of the blocking object At value 1 block At value 0 release At value 0 block At value 1 release Blocking object value before 1st communication 0 1 Behavio...

Страница 43: ...ge of mode may be triggered manually or automatically e g by a timer window contact The mode may be switched with two 8 bit objects of different priority Objects HVAC mode Prio 2 for switching in ever...

Страница 44: ...etpoint values You may enter separate setpoint values for each mode or use the comfort setpoint as a basic value Mode after reset Comfort Standby Eco Building protection Behaviour of the blocking obje...

Страница 45: ...en having guests The duration of this comfort extensi on period is set After the comfort extension period expires the system returns to eco mode Comfort Setpoint Comfort mode is usually used for dayti...

Страница 46: ...a basis If the comfort setpoint value is used as a basis the reduction increment of the value is set Eco setpoint Eco mode is usually used for night mode If setpoint values are entered separately A s...

Страница 47: ...you can decide whether to use a common control variable for heating and cooling If the 2nd level has a common control variable you also determine the control mode of the 2nd level here Starting heati...

Страница 48: ...which the maximum control variable value is reached i e the point at which maximum heating power is activated The reset time shows how quickly the controller responds to deviations from the set point...

Страница 49: ...common control variable for heating and cooling 0 is always transmitted as a fixed value 2 point control only level 2 2 point control is used for systems which are only set to ON or OFF When blocked...

Страница 50: ...tered or predetermined applications can be selected In the 2nd level therefore only for 2 level cooling cooling is controlled via a PI or a 2 point control In level 2 the setpoint deviation between th...

Страница 51: ...ntrol variable for heating and cooling 0 is always transmitted as a fixed value PI control with predetermined application This setting provides fixed parameters for a cooling ceiling Now specify what...

Страница 52: ...he objective is to prevent a too great a difference between indoor and outdoor temperature in order to keep the energy consumption low Activate the summer compensation Using the points 1 and 2 define...

Страница 53: ...llation for the sensor below point 1 the target value is in 0 1 C 0 500 200 above point 2 the target value is in 0 1 C 0 500 260 Send pattern periodically on change on change and periodically on chang...

Страница 54: ...Threshold value Set in which cases threshold values and delay times received are to be kept per object The parameter is only taken into consideration if the specification setting by object is activate...

Страница 55: ...until first call 1000 150000 60000 Object value limit min in Lux 1000 150000 Object value limit max in Lux 1000 150000 Type of threshold change Absolute value Increase decrease Increment in Lux upon...

Страница 56: ...red Use switching output block No Yes Analysis of the blocking object At value 1 block At value 0 release At value 0 block At value 1 release Blocking object value before first call 0 1 Action when lo...

Страница 57: ...s threshold values etc are related to the overall reading Night is recognised below Lux 1 1000 10 Hysteresis in Lux 0 500 5 Delays can be set via objects in seconds No Yes Switching delay on night non...

Страница 58: ...et the threshold value directly in the application program using parameters or define them via the bus using a communication object Threshold value setting using parameter Set the threshold values and...

Страница 59: ...t value limit min in 0 1 RH 1 1000 Object value limit max in 0 1 RH 1 1000 Type of threshold value change Absolute value Increase decrease Increment upon increase decrease change 0 1 RH 2 0 RH 20 0 RH...

Страница 60: ...lysis of the blocking object At value 1 block At value 0 release At value 0 block At value 1 release Blocking object value before first communi cation 0 1 Behaviour of the switching output On block Do...

Страница 61: ...lid until the first communication of a new setpoint value For units which have already been ta ken into service the last communicated setpoint value can be used Basically an air humidity range is spec...

Страница 62: ...ence between the two levels must be defined i e the setpoint value which when exceeded triggers the switch to the 2nd level Determine the deviation from the setpoint value at which the maximum variabl...

Страница 63: ...rature of the coolant which is based on the current dewpoint temperature offset deviation The switching output of the coolant temperature monitoring system can provide a warning prior to any build up...

Страница 64: ...eceived via communication object never after power supply restoration after power supply restoration and programming Start offset in C valid until first communication 0 200 30 Increment for offset cha...

Страница 65: ...periodically Send cycle is only sent if periodically is selected 5 s 10 s 30 s 2 h Use switching output block No Yes Analysis of the blocking object At value 1 block At value 0 release At value 0 bloc...

Страница 66: ...eresis 1 C Use absolute humidity No Yes Sending pattern never periodically on change on change and periodically At and above change of if sent on change 0 1 g 0 2 g 0 5 g 1 0 g 2 0 g 5 0 g Send cycle...

Страница 67: ...menus for the further setting of the computer are then displayed Use comparator 1 2 3 4 No Yes Output delivers Maximum value Minimum value Average value Use input 1 2 3 4 5 No Yes Output sends on cha...

Страница 68: ...supply restoration and programming Function I Input Prerequisite E1 E2 Prerequisite E1 E2 Prerequisite E1 E2 Prerequisite E1 E2 Prerequisite E1 E2 Prerequisite E1 E2 E3 Prerequisite E2 E1 E3 Prerequis...

Страница 69: ...t range depending on the type of output if the condition is not met 0 Input range depending on the type of output if the monitoring time period is exceeded 0 Input range depending on the type of outpu...

Страница 70: ...nitoring status should have if the monitoring period is exceeded without feedback Output value if applicable A1 A2 if the monitoring time period is exceeded 0 Input range depending on the type of outp...

Страница 71: ...tions are available for AND and OR logic Monitoring period 5 s 2 h 1 min Value of the object monitoring status if period is exceeded 0 1 Use block No Yes Analysis of the blocking object At value 1 blo...

Страница 72: ...the AND OR logic Output type a 1 Bit object two 8 bit objects Output value if logic 1 1 0 Output value if logic 0 1 0 Output value If block is active 1 0 Output value if monitoring period is exceeded...

Страница 73: ...hange of logic and periodically on change of logic to 1 and periodically on change of logic to 0 and periodically on change of logic object receipt on change of logic object receipt and periodically S...

Страница 74: ...ic input 12 inverted Logic input 13 Logic input 13 inverted Logic input 14 Logic input 14 inverted Logic input 15 Logic input 15 inverted Logic input 16 Logic input 16 inverted Temperature sensor malf...

Страница 75: ...re controller inactive Eco temperature controller active Eco temperature controller inactive Frost protection temperature controller active Frost protection temperature controller inactive Heating 1 t...

Страница 76: ...to those of the AND logic In addition the following inputs are available for the OR logic Switching output AND logic 1 Switching output AND logic 1 inverted Switching output AND logic 2 Switching outp...

Страница 77: ...GmbH Control and AutomationTechnology Sohlengrund 16 75395 Ostelsheim Phone 49 0 7033 30945 0 info elsner elektronik de Germany Fax 49 0 7033 30945 20 www elsner elektronik de Technical support 49 0...

Отзывы: