Parameter setting
Sensor Sewi KNX TH-L-Pr
• Version: 17.11.2016 • Technical changes and errors excepted.
Set, which objects will trigger interruption and when the regulation is to be continued.
Note: If the criteria for the continuation of the regulation are fulfilled, the regulation,
however, has just been stopped by an object or is blocked, then the end of the inter-
ruption has no effect on the behaviour of the light.
The light regulation can be
blocked
via the bus. In contrast to the interruption, when
blocking, a switching command or brightness value can be sent. Upon release, the out-
put behaviour follows the rule.
6.5.
Temperature Measurement
Select, whether a
malfunction object
is to be sent if the sensor is faulty.
Use
Offsets
to adjust the readings to be sent.
The unit can calculate a
mixed value
from its own reading and an external value. Set
the mixed value calculation if desired. If an external portion is used, all of the following
settings (threshold values, etc.) are related to the overall reading.
Use interruptions
No •
Yes
Interrupt regulation when
Reception from response switching object
No • Yes
Reception from response dimming object
No • Yes
Continue regulation
• after a waiting period
• at movement after waiting period
• at object reception after waiting period
• at object reception or after waiting period
• at movement after object reception
• at object reception or movement after
waiting period
Waiting period in seconds
5...72000
(Standard value depending on the
setting of "continue regulation")
Object value
0 • 1 • 0 or 1
Use block
No •
Yes
Analysis of the blocking object
• at value 1: block | at value 0: release
• at value 0: block | at value 1: release
Value prior to initial communication
0 • 1
Output pattern
On block
• send nothing
• send off command
• send on command
• send value
Use malfunction object
No • Yes
Offset in 0.1°C
-50…50; 0
Use external measured value
No • Yes