32
Parameter setting
Sensor Sewi KNX TH-L-Pr
• Version: 17.11.2016 • Technical changes and errors excepted.
The slave can be
blocked
via the bus.
6.3.1. Master 1/2/3/4
If the device is set as a master, the additional master settings 1 to 4 will appear. This
enables the
Sensor Sewi KNX TH-L-Pr
to perform four different control functions for
motion detection. Activate the master in order to use it.
Set, in which cases
threshold values and delay times
received via object are to be
retained. The parameter is only taken into consideration if the setting via object is ac-
tivated below. Please note that the setting "After power supply restoration and pro-
gramming" should not be used for the initial start-up, as the factory settings are always
used until the 1st communication (setting via objects is ignored).
Select, whether motion is to be detected
constantly or brightness dependent
.
Settings for brightness dependent motion detection:
The
brightness dependent motion detection
can be used via separate threshold
values for switch-on and switch-off or dependent on daylight. The separate threshold
values are ideal for controlling the light in rooms which are only illuminated by artifi-
cial light. The daylight dependent control is ideal for rooms with daylight and artificial
light.
For
daylight dependent motion detection with separate switch-on and
switch-off threshold values
activate, as required, the objects for setting the th-
reshold values. Then specify the switch-on and switch-off values (brightness range).
The switch-on value is the value, below which the room should be lit in the event of
Use block
No •
Yes
Analysis of the blocking object
• at value 1: block | at value 0: release
• at value 0: block | at value 1: release
Value prior to first communication
0 • 1
Use master 1/2/3/4
No • Yes
Maintain the
threshold values and delays received
via communication objects
• never
• after power supply restoration
• after power supply restoration and
programming
Motion detection
constantly • brightness dependent
Motion detection
brightness dependent
Type of brightness dependency
• separate switch-on and switch-off values
• daylight dependent