15

Parameter setting

Mixed gas sensor KNX VOC-UP basic

 • Version: 27.01.2020 • Technical changes reserved. Errors reserved.

Threshold value

Set the threshold values directly in the application program using parameters, or de-
fine them via the bus using a communications object.

Threshold value setpoint using parameter:

Set the threshold values and hysteresis directly.

Threshold value setpoint using a communications object:

Beforehand, enter how the threshold value will be received from the bus. Basically, a
new value can be received, or simply a command to increase or decrease.

During initial commissioning, a threshold value must be defined which will be valid un-
til the 1st communication of a new threshold value. For units which have already been
taken into service, the last communicated threshold value can be used. Basically, a
temperature range is given in which the threshold value can be changed (object value
limit).

A set threshold value will be retained until a new value or a change is transferred. The
current value is saved in EEPROM, so that this is retained in the event of a power sup-
ply failure  and will be available once the power supply is restored.

Switching output

Set the behaviour of the switching output when a threshold value is exceeded/under-
cut. The output switching delay can be set using objects or directly as a parameter.

Threshold value setpoint using

Parameter

 • Communications object

Threshold value in ppm

0...5000; 1200

Hysteresis of the threshold value in %

0 … 50; 20

Threshold value setpoint using

Parameter • 

Communications object

The last communicated value should be 
retained

• never 
• after restoration of power
• after restoration of power and 
  programming

Start threshold value

 

in ppm

valid till 1st communication

0...5000; 1200

Object value limit (min) in ppm

0...5000

Object value limit (max)

 

in ppm

0...5000

Type of threshold change

Absolute value • Increase/decrease

Step size 

(upon increase/decrease change)

1 • 2 • 5 • 10 • 20 • 50 • 100 • 200

Hysteresis of the threshold value in %

0 … 50; 20

Содержание KNX VOC-UP basic

Страница 1: ...KNX VOC UP basic Mixed Gas Sensor Item number 70244 white EN Installation and Adjustment...

Страница 2: ......

Страница 3: ...2 3 Composition 6 2 3 1 Housing 6 2 3 2 Rear view of sensor board with connections 7 2 4 Assembly of the sensor 7 2 5 Notes on mounting and commissioning 7 3 Addressing of the device at the bus 7 4 T...

Страница 4: ...eshooting of the device must only be carried out by a competent electrician Safety advice Safety advice for working on electrical connections components etc DANGER indicates an immediately hazardous s...

Страница 5: ...via an algorithm from the sum signal of all compounds included in the mixed gas Mixed value from own measured value and external value proportions can be set in percentage PI controller for ventilatio...

Страница 6: ...ervals To guarantee the accuracy on a sustained basis the sensor should be provided with fresh air at least once in 48 hours This occurs normally during room ventilation 1 1 2 Measuring ranges of diff...

Страница 7: ...f it can be assumed that risk free operation is no longer guaranteed The device is only to be used for its intended purpose Any improper modification or failure to follow the operating instructions vo...

Страница 8: ...the VOC content of the room air choose an installation position in height of head standing or sitting according to utilization of room When selecting an installation location please ensure that the m...

Страница 9: ...es on to the metal frame so that sensor and frame are fixed 2 5 Notes on mounting and commissioning Never expose the device to water e g rain or dust This can damage the electronics You must not excee...

Страница 10: ...bit 100 Maximum VOC reading Output R CT 0 2 bytes 101 Reset VOC maximum value Input WC 1 1 DPT_Switch 1 bit 102 VOC threshold value 1 Abso lute value Input Out put RWCT 0 2 bytes 103 VOC threshold val...

Страница 11: ...ut Out put RWCT 0 2 bytes 121 VOC threshold value 4 1 0 Input WC 1 1 DPT_Switch 1 bit 122 VOC threshold value 4 Swit ching delay from 0 to 1 Input WC 9 10 DPT_ Value_Time1 2 bytes 123 VOC threshold va...

Страница 12: ...ble comparator 2 Input 4 Input WC 5 1 DPT_Sca ling 1 byte 144 Actuating variable comparator 2 Input 5 Input WC 5 1 DPT_Sca ling 1 byte 145 Actuating variablecomparator 2 Output Output R CT 5 1 DPT_Sca...

Страница 13: ...5 5 xxx 1 byte 170 AND logic 6 Switching output block Input WC 1 1 DPT_Switch 1 bit 171 AND logic 7 1 bit switching out put Output R CT 1 1 DPT_Switch 1 bit 172 AND logic 7 8 bit output A Output R CT...

Страница 14: ...xx 1 byte 198 OR logic 5 Switching output block Input WC 1 1 DPT_Switch 1 bit 199 OR logic 6 1 bit switching out put Output R CT 1 1 DPT_Switch 1 bit 200 OR logic 6 8 bit output A Output R CT 5 5 xxx...

Страница 15: ...16 Logic input 6 Input WC 1 1 DPT_Switch 1 bit 217 Logic input 7 Input WC 1 1 DPT_Switch 1 bit 218 Logic input 8 Input WC 1 1 DPT_Switch 1 bit 219 Logic input 9 Input WC 1 1 DPT_Switch 1 bit 220 Logic...

Страница 16: ...VOC threshold values Activate the threshold values that you want to use here The Mixed gas sensor KNX VOC UP basic provides four threshold values for carbon dioxide Table of VOC values 1000 ppm corre...

Страница 17: ...ged object value limit A set threshold value will be retained until a new value or a change is transferred The current value is saved in EEPROM so that this is retained in the event of a power sup ply...

Страница 18: ...ot set using objects None 1 s 2 s 5 s 10 s 2 h Switching output sends on change on change to 1 on change to 0 on change and periodically on change to 1 and periodically on change to 0 and periodically...

Страница 19: ...he status object shows the current status of the output variable 0 OFF 0 ON and can for example be used for visualisation Switching output sends on change to 1 and periodically If switching output 1 s...

Страница 20: ...ch the target value can be changed object value limit A set target value will be retained until a new value or a change is transferred The cur rent value is saved in EEPROM so that this is retained in...

Страница 21: ...uld set the time appropriate to the ventilation system at this point follow the manufacturer s instructions Now determine what should be sent when the control is blocked On release the control variabl...

Страница 22: ...is selected 5 s 10 s 30 s 5 min 2 h From change of is only sent if on change of output is selected 1 2 5 10 20 25 Analysis of the blocking object at value 1 block at value 0 release at value 0 block a...

Страница 23: ...1 Logic output sends two 8 bit objects Type of objects Value 0 255 Percent 0 100 Angle 0 360 Scenario load 0 127 if logic 1 object A value Setting dependent on type of object if logic 0 object A valu...

Страница 24: ...not send message send value for logic 0 send value for logic 1 Value of the parameter Send behaviour Settings options Behaviour of the switching output on release on change of logic do not send messag...

Страница 25: ...ing output VOC 3 Switching output VOC 3 inverted Switching output VOC 4 Switching output VOC 4 inverted VOC controller status ventilation 1 VOC controller status ventilation 1 inverted VOC controller...

Страница 26: ...24 Parameter setting Mixed gas sensor KNX VOC UP basic Version 27 01 2020 Technical changes reserved Errors reserved AND logic output 8 AND logic output 8 inverted...

Страница 27: ......

Страница 28: ...bH Control and Automation Engineering Sohlengrund 16 75395 Ostelsheim Phone 49 0 70 33 30 945 0 info elsner elektronik de Germany Fax 49 0 70 33 30 945 20 www elsner elektronik de Technical support 49...

Отзывы: