8
Transfer protocol
Mixed gas sensor KNX VOC-UP basic
• Version: 27.01.2020 • Technical changes reserved. Errors reserved..
4.
Transfer protocol
Units:
VOC content in ppm
Variables in %
4.1.
List of all communications objects
Abbreviation flags:
C
Communication
R
Read
W Write
T
Transfer
U
Update
No.
Text
Function
Flags
DPT type
Size
0
Software version
readable
R-CT
0
2 bytes
2
VOC sensor malfunction
Output
R-CT
[1.1] DPT_Switch
1 bit
96
External VOC reading
Input
-WC-
0
2 bytes
97
Internal VOC reading
Output
R-CT
0
2 bytes
98
Total VOC reading
Output
R-CT
0
2 bytes
99
VOC maximum value request
Input
-WC-
[1.1] DPT_Switch
1 bit
100
Maximum VOC reading
Output
R-CT
0
2 bytes
101
Reset VOC maximum value
Input
-WC-
[1.1] DPT_Switch
1 bit
102
VOC threshold value 1: Abso-
lute value
Input/Out-
put
RWCT
0
2 bytes
103
VOC threshold value 1: (1:+ | 0:-)
Input
-WC-
[1.1] DPT_Switch
1 bit
104
VOC threshold value 1: Swit-
ching delay from 0 to 1
Input
-WC-
[9.10] DPT_-
Value_Time1
2 bytes
105
VOC threshold value 1: Swit-
ching delay from 1 to 0
Input
-WC-
[9.10] DPT_-
Value_Time1
2 bytes
106
VOC threshold value 1: Swit-
ching output
Output
R-CT
[1.1] DPT_Switch
1 bit
107
VOC threshold value 1: Swit-
ching output block
Input
-WC-
[1.1] DPT_Switch
1 bit
108
VOC threshold value 2: Abso-
lute value
Input/Out-
put
RWCT
0
2 bytes
109
VOC threshold value 2: (1:+ | 0:-)
Input
-WC-
[1.1] DPT_Switch
1 bit
110
VOC threshold value 2: Swit-
ching delay from 0 to 1
Input
-WC-
[9.10] DPT_-
Value_Time1
2 bytes
Содержание KNX VOC-UP basic
Страница 1: ...KNX VOC UP basic Mixed Gas Sensor Item number 70244 white EN Installation and Adjustment...
Страница 2: ......
Страница 27: ......