20
Parameter setting
Mixed gas sensor KNX VOC-UP basic
• Version: 27.01.2020 • Technical changes reserved. Errors reserved..
5.7.
Logic
Activate the logic inputs and assign object values up to 1st communication. Then, ac-
tivate the required logic outputs.
AND logic
OR logic
Output sends
• on change of output
• on change of output and periodically
• when receiving an input object
• when receiving an input object and peri-
odically
Send cycle
(is only sent if "periodically" is selected)
5 s • 10 s • 30 s • ... • 5 min • … • 2 h
From change of
(is only sent if "on change of output" is
selected)
1% • 2% • 5% • 10% • 20% • 25%
Analysis of the blocking object
• at value 1: block | at value 0: release
• at value 0: block | at value 1: release
Blocking object value
before 1st communication
0 • 1
Behaviour of the switching output
With blocking
• do not send message
• Send value
Sent value in %
0 ... 100
on release, output is sent
(with 2 seconds release delay)
• the current value
• the current value after receipt of an object
Use logic inputs
No •
Yes
Object value prior to 1. communication for:
Logic input 1... 16
0 • 1
Logic 1/2/3/4/5/6/7/8
not active • active
Logic 1/2/3/4/5/6/7/8
not active • active