6
Installation and commissioning
Mixed Gas Sensor KNX VOC-UP basic
• Version: 27.01.2020 • Technical changes reserved. Errors reserved.
The device may only be used as a fixed-site installation; that means only when
assembled and after conclusion of all installation and operational start-up tasks and
only in the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may occur
after publication of these operating instructions.
2.2. Installation position
The
Mixed Gas Sensor KNX VOC-UP basic
will be installed concealed within a
socket (Ø 60 mm, 42 mm deep).
May be installed and operated in dry interior rooms only.
Avoid condensation.
For monitoring of the VOC content of the room air choose an installation position in
height of head (standing or sitting, according to utilization of room).
When selecting an installation location, please ensure that the measurement results
are affected as little as possible by external influences. Possible sources of interference
include:
•
Drafts from windows and doors
•
Draft from ducts which lead from other rooms or from the outside to the
junction box in which the sensor is mounted
Measurement variations from such sources of interference must be corrected in the
ETS in order to ensure the specified accuracy of the sensor (offset).
To ensure a correct VOC measurement, the device must be installed in a windproof
socket.
2.3. Composition
2.3.1. Housing
Fig. 1
1
Notches
2
Air circulation holes
3
Programming LED (recessed)
4
Programming button (recessed)
for teaching instrument
5
Air circulation holes (BOTTOM)
2
1
4
3
5