13
Parameter setting
Mixed gas sensor KNX VOC-UP basic
• Version: 27.01.2020 • Technical changes reserved. Errors reserved.
5.
Parameter setting
5.1.
Behaviour on power failure/ restoration of
power
Behaviour following a failure of the bus power supply:
The device sends nothing.
Behaviour on bus restoration of power and following programming or reset:
The device sends all outputs according to their send behaviour set in the parameters
with the delays established in the "General settings" parameter block.
5.2.
General settings
Set the basic data transfer characteristics and select whether or not malfunction ob-
jects should be sent.
215
Logic input 5
Input
-WC-
[1.1] DPT_Switch
1 bit
216
Logic input 6
Input
-WC-
[1.1] DPT_Switch
1 bit
217
Logic input 7
Input
-WC-
[1.1] DPT_Switch
1 bit
218
Logic input 8
Input
-WC-
[1.1] DPT_Switch
1 bit
219
Logic input 9
Input
-WC-
[1.1] DPT_Switch
1 bit
220
Logic input 10
Input
-WC-
[1.1] DPT_Switch
1 bit
221
Logic input 11
Input
-WC-
[1.1] DPT_Switch
1 bit
222
Logic input 12
Input
-WC-
[1.1] DPT_Switch
1 bit
223
Logic input 13
Input
-WC-
[1.1] DPT_Switch
1 bit
224
Logic input 14
Input
-WC-
[1.1] DPT_Switch
1 bit
225
Logic input 15
Input
-WC-
[1.1] DPT_Switch
1 bit
226
Logic input 16
Input
-WC-
[1.1] DPT_Switch
1 bit
Send delay after power-up and programming for:
Measured values
5 s • ... • 2 h
Threshold values and switching outputs
5 s • ... • 2 h
Controller objects
5 s • 10 s • ... • 2 h
Logic outputs
5 s • 10 s • ... • 2 h
Maximum telegram quota
• 1 message per second
• ...
• 5 messages per second
• ...
• 20 messages per second
Use VOC malfunction object
Yes • No
No.
Text
Function
Flags
DPT type
Size