![Elsner KNX VOC-UP basic Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/elsner/knx-voc-up-basic/knx-voc-up-basic_installation-and-adjustment-manual_2396524007.webp)
5
Installation and commissioning
Mixed Gas Sensor KNX VOC-UP basic
• Version: 27.01.2020 • Technical changes reserved. Errors reserved.
* corresponding concentration range based on lab measurements at gas mixing system with synthetic air at 50% r.h. and RT
2.
Installation and commissioning
2.1. Installation notes
Installation, testing, operational start-up and troubleshooting should
only be performed by an electrician.
CAUTION!
Live voltage!
There are unprotected live components inside the device.
•
National legal regulations are to be followed.
•
Ensure that all lines to be assembled are free of voltage and take
precautions against accidental switching on.
•
Do not use the device if it is damaged.
•
Take the device or system out of service and secure it against
unintentional use, if it can be assumed, that risk-free operation is no
longer guaranteed.
The device is only to be used for its intended purpose. Any improper modification or
failure to follow the operating instructions voids any and all warranty and guarantee
claims.
After unpacking the device, check it immediately for possible mechanical damage. If it
has been damaged in transport, inform the supplier immediately.
Compound
Formula
Range*
(ppm)
Potential sources of pollutants
indoors
Carbon monoxide
CO
0-10
Car exhaust, fuel-based heating, cook-
ing appliances, smoking
Methane
CH
4
0-200
Natural gas
Propane
C
3
H
8
0-20
Fuel-based heating, cooking appli-
ances, cleaners
Ethyl alcohol
C
2
H
6
O
0-3
Cosmetics, cleaners, disinfectants,
detergents, paints, coatings, breath
Acetaldehyde
C
2
H
4
O
0-20
Adhesives, coatings, plastics,
lubricants, ripening of fruits
Methylethylketone
C
4
H
8
O
0-20
Adhesives, coatings, plastics,
lubricants
Toluene
C
7
H
8
0-5
Paints, coatings, cleaners, detergents,
smoking, polyurethane lacquers