20
Transmission protocol
Ultrasonic Probe KNX SO250
• Version: 14.09.2020 • Technical changes and errors excepted.
6.
Transmission protocol
6.1. Listing of all communication objects
Abbreviations
EIS types:
EIS 1 Switching 1/0
EIS 5 Floating decimal value
EIS 6 8 bit value
EIS 9 Float value
Flags:
C Communication
R Read
W Write
T Transmit
U Update
No. Name
Function
EIS-
type
Flags
0
Measured value in Litres
Output
5
C R T
1
Measured value in m³
Output
9
C R T
2
Measured value in %
Output
6
C R T
3
Measured value in m
Output
9
C R T
4
Measured value request
Input
1
C R W
5
Lock measurement
Input
1
C R W
6
Sensor fault
Output
1
C R T
7
Min/max adjustment
Input
1
C R W
8
Request max fill level
Input
1
C R W
9
Max fill volume in Litres
Output
5
C R T
10
Max fill volume in m³
Output
5
C R T
11
Threshold value 1 in litres: 16 bit value
Input / Output
5
C R W T U
12
Threshold value 1 in m³: 16 bit value
Input / Output
9
C R W T U
13
Threshold value 1 in %: 16 bit value
Input / Output
5
C R W T U
14
Threshold value 1 in m: 16 bit value
Input / Output
9
C R W T U
15
Threshold value 1: 1 = increase |
0 = decrease
Input
1
C R W
16
Threshold value 1: increase
Input
1
C R W
17
Threshold value 1: decrease
Input
1
C R W
18
Threshold value 1: switching output
Output
1
C R T
19
Threshold value 1: switching output lock
Input
1
C R W
20
Threshold value 2 in litres: 16 bit value
Input / Output
5
C R W T U
Содержание 70151