Settings on the device
Ultrasonic Probe KNX SO250
• Version: 14.09.2020 • Technical changes and errors excepted.
Press key to confirm your selection and continue as described in “Settings for all
tank designs“.
4.3.5. Settings for all tank designs
Setting options: From 1 s to 9 s in increments of one second, from 10 s to 50 s in incre
-
ments of ten seconds, from1 min to120 min in increments of 10 minutes.
Press key to confirm your selection. You will automatically return to the standard
screen.
Please enter the
inside diameter
of the tank:
200cm ™
Use the keys
and
to select the inside diame
-
ter of the tank (1 to 1000 cm).
Please enter the probe
distance
to the liquid for
a full tank: 15cm™
Use the keys and to select the distance of the
probe to the liquid for full tank (12 to 200 cm).
Press key to confirm your selection.
Please enter the number
of tanks
in a battery:
2 tanks ™
Use the keys
and
to select how many of the
described tanks exist in one battery (1 to 100
tanks). Press key to confirm your selection.
Display in Litres >™
Display in m
3
>
Display in %
>
Move the cursor to the required setting using the
keys
or
. The KNX SO250 can indicate the
tank fill volume in Litres (l), cubic metres (m³) or
percent (%). Press key
to confirm your selec
-
tion.
Measurement frequency?
Once every 8 sec.™
Use the keys
and
to specify the required
time interval for the measurements.