105U-G Wireless Gateway
User Manual
Page 135
© September 2004
Press “Enter” to go back to the menu.
Option b) Write Image Array
This option allows you to change the value of an I/O register in the Radio Interface.
To change the value of a register, select option b) write image array.
Enter the location, then the value to be written to the register – for example
b
Location:
12
New Value: 0x
FFFF
Register values should always be written in hexadecimal format. If you want the 105G to stop
the host device reading or writing values to the I/O database at the same time, then select
option h) or i).
Options c), d) Enable/Disable Comms logging
These options allow logging and display of radio communications. Once enabled, the radio
communications that are displayed is the radio traffic in raw format (i.e. the raw data frame
for each received packet is displayed in hexadecimal format). To decode the meaning of each
radio data packet, configuration software can be used to decode the data frames.
To decode the radio traffic using configuration software, first start communications logging
by selecting option “c) Enable Comms Logging” from the debug menu. Next, in the
diagnostics screen select ‘Stop Terminal’ and then ‘Start Comms’. Configuration software