FAP54 Installation                                                 

    

 

 

CONFIGURATION CIRCUIT: XX   TYPE: XXXXX 
TOT. PTS: XXX  
  XXX/SM  XXX/HT  XXX/MU  XXX/MC 

  XXX/MN  XXX/GS  XXX/LN  XXX/SH

      

    

CONFIGURATION STORED 
[1]    DELETE ALL THE ASSOCIATIONS 
[2]    DELETE EXPIRED ASSOCIATIONS 
[ESC]  BACK 

CONFIGURATION CIRCUIT: XX   TYPE: XXXXX 
TOT. PTS: XXX  

  XXX/LI  XXX/PI  XXX/XS  XXX/TB

      

 

  XXX/CI  XXX/IS  XXX/ER  XXX/?? 

ERROR ON CIRCUIT: XX 
ERROR CODE: YYY 
ADDRESS/POSITION: ZZZ 
 

FAULT ON CIRCUIT: XX   
BMP1: 01234567       BMP2: 01234567 
      ----**--              *-*----- 
TYPE: XXXX           A = D---  B = D--- 

FAULT ON CIRCUIT MODULE XX 
ERROR CODE: YYY 

 

By pressing OK, the control panel is informed that the procedure is finished (the operator has removed and then re-
inserted each single device in the order he wanted them to be addressed). 

 

In this last case the screen will display the devices initialized up to that moment, subdivided per type and number. 

 
 
 
 
 

 

 
 
 

 

 
By pressing ESC the configuration is cancelled. By pressing OK the new configuration is confirmed and stored. 

 

At the end of storage, it is possible to delete all the associations or only the ones no longer valid: 

 
 
 
 
 
 
 

During the initialization procedure, regardless of the type of selected initialization, a module fault could occur. In such 
a case, the procedure will be interrupted and the following message will be displayed with: 

 

The number of the circuit connected to the line affected by the fault 

 

The error code (please, refer to Appendix 1 for further details) 

 
 
 
 
 
 
If a procedure error occurs during the initialization procedure, it will be interrupted and the following message will be 
displayed with: 

 

The number of the circuit connected to the line affected by the fault 

 

The error code (please, refer to Appendix 2 for further details) 

 

The address or physical position of the device  which has generated the error (depending on the procedure, 
this  information  could  be  present  or  not  and,  in  the  case  it  is  present,  its  meaning  is  strictly  related  to  the 
procedure) 

 
 
 
 
 
 
 

 
If  an  error  related  to  the  detection  line  (concerning  specifically  the  field)  occurs  ,  the  following  message  is  displayed 
(please, refer to appendix 3 for further details): 
 
 
 
 
 
 
 

Содержание FAP54

Страница 1: ...DS80SC61 002I LBT80099 Installation manual GB FAP54 Multiprocessor modular control panel for fire detection 00 51 09 ...

Страница 2: ...lease contact your local city office your household waste disposal service or the shop where you purchased the product The information contained in this document has been collected and controlled carefully However the company cannot be held responsible for any possible errors and omissions The company reserves the right to make at any time and without warning improvements and modifications to the ...

Страница 3: ...YOUT OF FAP54 16 INTERNAL MODULES 11 3 FAP54 COMPONENTS 12 3 1 FRONT PANEL OF FAP541 12 3 2 FRONT PANEL OF FAP544 FAP548 FAP5416 13 3 3 KEYPAD 14 3 4 LED INDICATORS ON THE FRONT PANEL 14 3 5 FAP ELECTRICAL SPECIFICATIONS 16 3 6 FAP54 CPU BOARD 17 3 7 FAP54 CONTROL AND COMMAND BOARD 18 3 8 EXAMPLES OF FAP54 TERMINAL BOARD CONNECTION 19 3 9 FAP54 BATTERY CHARGER BOARD 20 3 10 FA128 LINE MODULE 21 3 ...

Страница 4: ...evice shall be fitted by the installer inside an electric cabinet which might include also other devices therefore it shall be suitably identified 1 1 3 Batteries The control panel has an internal power source provided by two sealed lead batteries ATTENTION Danger of explosion if the batteries are replaced with the wrong type Remove used batteries following the instructions provided The batteries ...

Страница 5: ...trol panel described in this manual has been developed according to the quality reliability and performance criteria used by ELKRON Every component can operate according to the EN54 2 and EN54 4 standards 1 5 LIST OF OPTIONS WITH REQUIREMENTS 7 8 Output to fire alarm device 7 9 Output to fire alarm routing equipment 7 11 Delay to outputs 7 12 Co incidence detection 8 3 Fault signals from points 8 ...

Страница 6: ...6 FAP54 Installation 2 FAP54 OVERALL DIMENSIONS Figure 1 Internal view and hole template for fastening to the wall ...

Страница 7: ... on the AC DC converter Then fasten the cable properly with a small band For the supply cable a manually operated power supply switching device externally to the control panel must be used this switching device must have a 3 mm minimum distance between contacts The switching equipment must disconnect simultaneously the Line and the Neutral conductor After powering the control panel on connect the ...

Страница 8: ...8 FAP54 Installation 2 5 LAYOUT OF FAP54 01 INTERNAL MODULES ...

Страница 9: ...FAP54 Installation 9 2 6 LAYOUT OF FAP54 04 INTERNAL MODULES ...

Страница 10: ...10 FAP54 Installation 2 7 LAYOUT OF FAP54 08 INTERNAL MODULES ...

Страница 11: ...FAP54 Installation 11 2 8 LAYOUT OF FAP54 16 INTERNAL MODULES ...

Страница 12: ...12 FAP54 Installation 3 FAP54 COMPONENTS 3 1 FRONT PANEL OF FAP541 ...

Страница 13: ...FAP54 Installation 13 3 2 FRONT PANEL OF FAP544 FAP548 FAP5416 The front panel contains the following components display alphanumeric keypad keys LEDs ...

Страница 14: ...ed by 1 minute The maximum overall time initial delay increments due to the key is 10 minutes Whenever the user presses this key an event is stored in the event log and if the passwords are enabled the level 2 password is required MASTER ALARM When the control panel is in monitoring phase this key triggers the general alarm condition Whenever the user presses this key an event is stored in the eve...

Страница 15: ...hat the maintenance procedure has found one or more smoke detectors which require maintenance TEST SYSTEM YELLOW When ON it indicates that a zone test is in progress MAIN BATTERY GREEN Steady ON the control panel is powered on by the main AC Blinking the control panel is powered on by batteries EXCLUSIONS LINE YELLOW When ON it indicates that one or more circuits are excluded ZONE YELLOW When ON i...

Страница 16: ...ries fuse Maximum current provided by batteries with AC power supply disconnected Maximum battery internal resistance 2x12V 12 Ah F4AL 250V 4 0 A Rimax 0 8 Ω Operating temperature 5 C 40 C Pollution grade Grade 2 Overvoltage category CAT II NA NC outputs Fire alarm Siren activated Faults Programmable Missing AC Exclusions Controlled outputs Siren max 500mA Self powered siren max 250 mA RS232 RS485...

Страница 17: ...TES The following optional modules are not covered by the EN54 2 standard MODEM MODULES MPSTN500 PSTN and MGSM500 GSM LAN MODULE LAN TCP IP500 232 485 MODULE RS232 RS485 IT USB KEY MODULE for connection via JP17 with external mass storage USB key ...

Страница 18: ...C are meant to be idle NOT armed The fault relay is normally energized when the control panel is powered on in case of fault the relay is released The relay outputs PROG RL1 RL2 and FAULT must NOT be used to command output devices of type C E J G and transmission devices ...

Страница 19: ...s on the control and command board If a self powered siren output is used connect a 10KΩ end line resistor with the siren terminals see figure If no self powered siren output is used connect a 10KΩ resistor with the self powered siren output terminals on the control and command board If no external power supply is connected make a jumper between PS CTRL terminals he resistors and jumper are mounte...

Страница 20: ... handles the recharge of two lead acid batteries connected in series As to performance it complies with EN54 4 NOTE in case of connection of additional power supply units connect the negative terminal of the additional power supply unit with the negative terminal of the control panel power supply unit ...

Страница 21: ...of the following control panels FAP54 04 FAP54 08 FAP54 16 It can be inserted in any free slot of the Backplane and its configuration is completely automatic without the need to set the address The presence on board of the short circuit insulator ensures the best protection against possible faults due to the detection line The FA128 line module can be configured by the control panel both with open...

Страница 22: ...Co incidence detection 8 3 Fault signals from points 8 9 Output to fault warning routing equipment 9 5 Disablement of addressable points 10 Test condition 0051 09 0051 is a trademark of URMET S p A Via Bologna 188 C 10154 Torino Italy 09 0051 CPR 0238 DoP n 0051 CPR 0238 FAP548 Fire detection and fire alarm control panel EN 54 2 1997 A1 2006 EN 54 4 1997 A1 2002 A2 2006 100 240 V 15 10 50 60 Hz 3 ...

Страница 23: ...lation 23 4 DETECTION LINES 4 1 LOOP LINE CONNECTION CLASS A M9 JP2 JP1 IN SHIELD OUT I N 2 I N1 NC C NO PWR I C Figure 2 Device connection on loop line class A Shield to be connected to earth on the control panel ...

Страница 24: ...le with reference to Figure 2 if a short circuit occurs between device 2 and device 3 the action of the insulators enables the system to isolate the line section between the devices under consideration Device 2 will be powered by side A of the line module while device 3 will be powered by side B of the line module No device will be lost and the short circuit will be isolated Instead if the short c...

Страница 25: ...ows a series type connection The picture on the right shows a parallel type connection Note that the execution of autoaddressing procedures on series type connections guarantees the assignment of consecutive addresses to the points Shield to be connected to earth on the control panel Shield to be connected to earth on the control panel ...

Страница 26: ...total resistance less than 100 Ω NOTE the max total length of the open line is the sum of the lengths of all the branches To find out the line cable resistance short circuit the two wires at each branch terminal and then use an ohmmeter to measure the wires to be connected with the control panel terminals NOTE if on the detection line there are short circuit insulators they shall be removed before...

Страница 27: ... DEVICE See the programming manual for further details In case of automatic addressing it is possible to address one single line address simultaneously all the lines In both cases it is necessary to define the type of line Open Loop To enable automatic addressing follow the steps below Press the menu key Select programming option 1 Press OK to confirm selection Select 1 to select the Circuit menu ...

Страница 28: ...tialization is used in case of system expansion The previous points already configured are not changed while the new ones are automatically assigned a valid address starting from the first available one If any point of the previous configuration is removed the control panel will automatically assign the address of the removed point to a new device If the auto addressed mode is selected a further c...

Страница 29: ... the failure reasons The initialization procedure consists of sub procedures some of which usually the most burdensome in terms of time can be interrupted by the user The user is allowed to interrupt abort a procedure when the following message is shown If the procedure is interrupted by the user the control panel will carry out the following operations on each module restore of the previous confi...

Страница 30: ...e devices with valid addresses range 1 128 A new or non configured device is not accepted by the control panel which will abort the procedure Update this type of initialization is used in case of system expansion The points already configured are not changed while the new ones are automatically assigned a valid address starting from the first available one If any addresses of the previous configur...

Страница 31: ... communication problems with the control panel or devices with duplicated addresses The type refers to a device whose address is recognized by the control panel but whose type is not valid for the control panel By pressing ESC The configuration before initialization is restored if the pre configured or update mode is selected The configuration is cancelled if the self addressed mode is selected By...

Страница 32: ...e end of storage it is possible to delete all the associations or only the ones no longer valid During the initialization procedure regardless of the type of selected initialization a module fault could occur In such a case the procedure will be interrupted and the following message will be displayed with The number of the circuit connected to the line affected by the fault The error code please r...

Страница 33: ... the previous configuration if the pre configured or update initialization mode has been selected cancellation of the configuration if the auto addressed or walk addressing initialization mode has been selected Therefore if the user interrupts the initialization procedure in auto addressed or walk addressing mode any configuration stored in the module before the start of initialization procedure w...

Страница 34: ...t 7 Unexpected answer from the module 1 8 Unexpected answer from the module 1 9 Unexpected answer from the module 1 10 Unexpected answer from the module 1 11 Unexpected answer from the module 1 12 Unexpected answer from the module 1 13 Module is blocked 1 14 Module not usable because of a serious line fault e g short circuit overload 15 Fault in the module transmitter 16 Fault in the module transm...

Страница 35: ...ing the address assignment phase Check the electrical connections after the point 12 Auto addressed loop mode initialization point with random address not found Check the electrical connections 13 Procedure stopped by the control panel a stop command has been received 20 Pre configured loop mode initialization line fault overload or shortcircuit at power on Check the electrical connections among t...

Страница 36: ...a point with invalid address The module could not communicate with the point check the electrical connections 66 Auto addressed open mode initialization no answer from a point with valid 1 128 address The module could not communicate with the point check the electrical connections 67 Auto addressed open mode initialization Missing answer from a point with valid 1 128 address The module could not c...

Страница 37: ...cedure line fault overload or shortcircuit at power on Check the electrical connections among the circuit line card and the points connected directly with LA and LB 206 Type match verification procedure mismatch between the configuration stored in the control panel and the configuration in the field 207 Search short circuit line fault overload or shortcircuit at power on Check the electrical conne...

Страница 38: ...he bits set are represented by asterisks and indicate the faults occurred according to the following decoding table BMP1 Bit 0 Fault on circuit A 1 isolated at terminals LA for short circuit overload Bit 1 Fault on circuit B 2 isolated at terminals LB for short circuit overload Bit 2 Fault on circuit A 1 isolated at the point XXX for short circuit overload Bit 3 Fault on circuit B 2 isolated at th...

Страница 39: ...FAP54 Installation 39 ...