FAP54 Installation
15
INDICATOR
COLOR
FUNCTION
A
L
A
R
M
S
FIRE ALARM
RED
Blinking: the control panel is in alarm condition and the siren
output is not active.
Fixed ON: the control panel is in alarm condition and the siren
output is active.
MASTER ALARM
RED
When turned ON, a general alarm condition has occurred.
M
O
D
EM
MODEM ACTIVE
RED
Blinking: the modem is attempting to setup a call.
Steady ON: the modem connection is active.
Steady OFF: the modem is not performing any activity.
MODEM STATE
YELLOW
Blinking: fault on the transmission line.
Fixed ON: modem (or part of its functionality) excluded.
F
A
U
L
T
S
GENERAL
YELLOW
When turned ON, it indicates a Fault condition. Further
information on the type of fault is provided through the display
and the dedicated LEDs. This LED provides a cumulative fault
indication.
SYSTEM
YELLOW
When turned ON, it indicates a system fault. Usually, when
this LED is ON it indicates a fault affecting the CPU of the
control panel.
BATTERY
YELLOW
When ON, it indicates a control panel battery fault or
malfunctioning.
SIREN
YELLOW
When ON, it indicates a fault on the line controlling the siren or
a fault on an actuator driving an alarm signalling device (“C”
type).
EARTH
YELLOW
When ON, it signals an earth dispersion.
M
A
IN
T
EN
A
N
C
E
MAINTENANCE
YELLOW
When ON, it indicates that the maintenance procedure has
found one or more smoke detectors which require
maintenance.
TEST SYSTEM
YELLOW
When ON, it indicates that a zone test is in progress.
MAIN/BATTERY
GREEN
Steady ON: the control panel is powered on by the main AC.
Blinking: the control panel is powered on by batteries.
EXC
L
U
SI
O
N
S
LINE
YELLOW
When ON, it indicates that one or more circuits are excluded.
ZONE
YELLOW
When ON, it indicates that one or more zones are excluded.
GROUP
YELLOW
When ON, it indicates that one or more groups of points or
groups of zones are excluded.
DEVICE
YELLOW
When ON, it indicates that one or more points are excluded.
SIREN
YELLOW
When ON, it indicates the exclusion of a siren or an actuator
driving an alarm signaling device (“C” type).
DISCHARGE
YELLOW
When ON, it indicates the exclusion of an actuator driving fire-
extinction equipment (“G” type).
G
EN
ER
A
L
EXCLUSION
YELLOW
When ON, it indicates that something is excluded in the control
panel. This is an exclusion cumulative indicator.
REMOTE DEVICE
YELLOW
When ON, it indicates a communication error during
communication with an LCD annunciator or a SLAVE control
panel, or a communication problem during communication with
a PC via modem or LAN.
SILENCE SIREN
YELLOW
When ON, it indicates that the siren output has been turned off
by using the SILENCE SIREN key.
ACTION DELAYED
YELLOW
When ON, it indicates that the timer of a zone or group in time
mode is running or has expired and the zone or group has
undergone an alarm condition.
Содержание FAP54
Страница 8: ...8 FAP54 Installation 2 5 LAYOUT OF FAP54 01 INTERNAL MODULES ...
Страница 9: ...FAP54 Installation 9 2 6 LAYOUT OF FAP54 04 INTERNAL MODULES ...
Страница 10: ...10 FAP54 Installation 2 7 LAYOUT OF FAP54 08 INTERNAL MODULES ...
Страница 11: ...FAP54 Installation 11 2 8 LAYOUT OF FAP54 16 INTERNAL MODULES ...
Страница 12: ...12 FAP54 Installation 3 FAP54 COMPONENTS 3 1 FRONT PANEL OF FAP541 ...
Страница 39: ...FAP54 Installation 39 ...