FAP54 Installation
7
2.1 FASTENING THE FAP CONTROL PANEL TO THE WALL
The FAP control panel must be fastened to the wall at a suitable height in order to facilitate the reading of display and
access for the operator.
If the control panel is installed near a corner, verify that the front panel can be opened without any difficulty.
The control panel is fastened to the wall by means of 4 screw anchors with maximum dimension of 6 mm.
Do not install the control panel near heat sources (radiators, convectors, heating plants, etc.)
After the fixing holes are made in the wall, open the front panel by removing the blocking screw, pass the cables
coming from the field through the holes in the rear of the cabinet and fasten the control panel to the wall with suitable
screws.
Connect the cables coming from the field to the control panel by avoiding to put them too close to the power supply
cable.
Pass the power supply cable through the suited hole put in the bottom of the cabinet, on the left (near the AC/DC
converter).
2.2 CONNECTING THE FAP CONTROL PANEL TO THE AC POWER SUPPLY
The connection must be carried out with a sheathed cable with 3 conductors (line – neutral – earth).
Remove the sheath from the cable and connect the conductors L, N and Earth to the correspondent terminals on the
AC/DC converter. Then, fasten the cable properly with a small band.
For the supply cable, a manually operated power supply switching device externally to the control panel must be used;
this switching device must have a 3 mm minimum distance between contacts.
The switching equipment must disconnect simultaneously the Line and the Neutral conductor.
After powering the control panel on, connect the batteries to the correspondent terminals located on the command and
control board and place the thermal probe on the batteries. This probe is used to compensate the charging voltage of
the batteries when the temperature changes.
2.3 MAINTENANCE
Periodically clean the keypad and the display window by using a wet cloth.
Do not use any detergent or solvent product for cleaning.
Periodically check the LEDs functionality by using the relevant function from the control panel’s menu.
After system start-up, set the desired interval of periodic execution of the automatic maintenance procedure, which
monitors the cleaning level of the smoke detectors, by signalling the ones needing maintenance.
2.4 BATTERIES
In the control panel must be used two rechargeable batteries of 12 V, 12 Ah connected in series.
The batteries must:
•
Have the same model/capacity
•
Be of VRLA (Valve Regulated Lead Acid) type
•
Have a case with UL94V-1 or better flame rating
•
Be compliant with IEC 60896-21:2004, IEC 60869-22:2004 standards
The batteries replacement must be performed on by qualified personnel.
Содержание FAP54
Страница 8: ...8 FAP54 Installation 2 5 LAYOUT OF FAP54 01 INTERNAL MODULES ...
Страница 9: ...FAP54 Installation 9 2 6 LAYOUT OF FAP54 04 INTERNAL MODULES ...
Страница 10: ...10 FAP54 Installation 2 7 LAYOUT OF FAP54 08 INTERNAL MODULES ...
Страница 11: ...FAP54 Installation 11 2 8 LAYOUT OF FAP54 16 INTERNAL MODULES ...
Страница 12: ...12 FAP54 Installation 3 FAP54 COMPONENTS 3 1 FRONT PANEL OF FAP541 ...
Страница 39: ...FAP54 Installation 39 ...