30
FAP54 Installation
CIRCUIT:
[1] SET SINGLE CIRCUIT IN LOOP MODE
[2] SET SINGLE CIRCUIT IN OPEN MODE
[1] AUTO-ADDRESSED MODE
[2] PRE-CONFIGURED MODE
[3] UPDATE
[1] AUTO-ADDRESSED MODE
[2] PRE-CONFIGURED MODE
[3] UPDATE
[4] WALK ADDRESSING
WARNING! THIS PROCEDURE AFFECTS
THE ADDRESSES OF THE DEVICES
[OK] CONTINUE [ESC] BACK
5.2 CONFIGURE SINGLE CIRCUIT
The user is asked to insert the number of the circuit to be initialized:
After entering and confirming with OK the circuit number, the user is asked for the type of configuration:
After selecting the circuit configuration, the initialization mode is requested.
The initialization modes depend on the circuit configuration.
If the loop configuration has been selected, the following circuit configuration menu is displayed:
If the open configuration is selected, the following options are displayed:
Auto-addressed mode: the whole set of points is re-addressed according to the physical position occupied by the
single point. The previous addresses are replaced by new addresses assigned by the control panel.
Pre-configured mode: the points in the field are acquired by the control panel without any change in their address.
However, the control panel accepts only the devices with valid addresses (range 1-128). A new or non-configured
device is not accepted by the control panel which will abort the procedure.
Update: this type of initialization is used in case of system expansion. The points already configured are not changed,
while the new ones are automatically assigned a valid address, starting from the first available one. If any addresses
of the previous configuration are removed, the control panel will automatically assign the address of the removed point
to a new device.
Walk addressing: this type of initialization is carried out by removing and then reconnecting the points, one by one.
The points will be assigned the addresses in the order they have been removed.
The condition required to enable this type of initialization is that all the devices are already wired and connected in
pure parallel (if modules or pushbuttons are used, insert the input/output short circuit jumper).
The operator shall remove one device at a time, keep it removed for at least 5 seconds and then put it back (for
pushbuttons and modules, remove the related power supply jumper). After the device has been reconnected, wait for
the green LED blinking to confirm the address assignment.
For the auto-addressed mode the same considerations made in the case of configuration of all the circuits can be
applied. The user will be asked for a further confirmation before proceeding:
Содержание FAP54
Страница 8: ...8 FAP54 Installation 2 5 LAYOUT OF FAP54 01 INTERNAL MODULES ...
Страница 9: ...FAP54 Installation 9 2 6 LAYOUT OF FAP54 04 INTERNAL MODULES ...
Страница 10: ...10 FAP54 Installation 2 7 LAYOUT OF FAP54 08 INTERNAL MODULES ...
Страница 11: ...FAP54 Installation 11 2 8 LAYOUT OF FAP54 16 INTERNAL MODULES ...
Страница 12: ...12 FAP54 Installation 3 FAP54 COMPONENTS 3 1 FRONT PANEL OF FAP541 ...
Страница 39: ...FAP54 Installation 39 ...