![ELKHART BRASS Cobra 7250 HD EXM Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/elkhart-brass/cobra-7250-hd-exm/cobra-7250-hd-exm_installation-operating-and-maintenance-instructions_2393094037.webp)
37
5.1-5.7
6 bits
Reserved
6
1 byte
Group Number of Input Controller sending message (1-15)
7
1 byte
Reserved
Monitor Position Feedback Message
Repetition rate:
100mS
Data Length:
8
Extended Data Page:
0
Data Page:
0
PDU Format:
255
PDU Specific:
240
Default Priority:
6
Parameter Group Number: 255,240 (0x00FFF0) – broadcast message
Start Position Length
Parameter
0
1 byte
0xFD – Command
1
2 bytes
Horizontal Position Feedback (0000-3600)
0000 corresponds to the left most allowable operating
position.
1/10 degree resolution
High byte is byte 1, Low byte is byte 2
3
2 bytes
Vertical Position Feedback (0000-3600)
0000 corresponds to straight up when monitor is mounted
vertically.
1/10 degree resolution
High byte is byte 3, Low byte is byte 4
5.0
1 bit
1 for at left keep out area, 0 for not at left keep out area
5.1
1 bit
1 for at right keep out area, 0 for not at right keep out area
5.2
1 bit
1 for at left programmed limit, 0 for not at left programmed limit
5.3
1 bit
1 for at right programmed limit, 0 for not at right programmed
limit
5.4
1 bit
1 at top limit, 0 for not at top limit
5.5
1 bit
1 for bottom limit, 0 for not at bottom limit
5.6
1 bit
1 for in Extended Travel region, 0 for not in Extended Travel
region
5.7
1 bit
1 for Extended Travel enabled, 0 for Extended Travel disabled
6.1
1 bit
Power/CAN cable pin 3 state (0 = grounded, 1 = not
grounded)
6.2
1 bit
Power/CAN cable pin 4 state (0 = grounded, 1 = not
grounded)
6.3-6.7
6 bits
Reserved
7
1 byte
Reserved