If the Stow Module will be a termination point (at the extreme end of your main
CAN line), install the supplied jumper between positions 8 & 9 of the Stow
Module Harness.
Connect the Stow indicator leads of the
Stow Module Harness to the customer
supplied devices that the Stow Module is to
actuate.
o
The Stow Module provides a ground to
these leads when the EXM monitor is not
stowed, and provides an open circuit
otherwise.
o
The Stow Lamp lead (position 4) can
be used to switch a light or device
with a low current draw. There is a
100ohm current-limiting resistor on this
signal so that this lead could be
directly connected to an LED. (Seal
lead if unused)
o
The Stow Signal lead (position 5) can be used to switch a device that may
require more current or one that you want to maintain the switch state when the
Stow Module is powered off. (Seal lead if unused)
Supply power to the Stow Module by connecting the RED (power) and BLACK
(ground) leads to an appropriate power source.
Install a 1 Amp fuse into the positive power lead for a 12V system (1/2 Amp for 24V
system).
Electric Actuated Unibody Valve –
2a
1
2b
1
2
Jumper
Jumper