INTERNAL CONNECTIONS FOR S65
Signal Type
of
connection
Cable
marking
Component Board Connector Component Board Connector
Control signals,
supply module 1
9-pole
screened cable
C-PS1
Control unit
ES842
CN4
Supply module 1
ES840
CN8
Control signals,
supply module 2 (*)
9-pole
screened cable
C-PS2
Control unit
ES842
CN3
Supply module 2
ES840
CN8
Control signals,
Inverter module U
9-pole
screened cable
C-U
Control unit
ES842
CN14
Inverter module U ES841
CN3
Control signals,
Inverter module V
9-pole
screened cable
C-V
Control unit
ES842
CN11
Inverter module V ES841
CN3
Control signals,
Inverter module W
9-pole
screened cable
C-W
Control unit
ES842
CN8
Inverter module W ES841
CN3
+24V Power supply,
control unit
Unipolar
cable, 1mm
2
Supply module 1 ES840 MR1-1 Control
unit ES842 MR1-1
0V Power supply,
control unit
Unipolar
cable, 1mm
2
24V-CU Supply module 1 ES840 MR1-2 Control
unit ES842 MR1-2
+24VD Power supply,
driver boards ES841
Unipolar
cable, 1mm
2
Supply module 1 ES840 MR1-3 Inverter
module
U
ES841 MR1-1
0VD Power supply,
driver boards ES841
Unipolar
cable, 1mm
2
24V-GU Supply module 1 ES840 MR1-4 Inverter
module
U
ES841 MR1-2
+24VD power supply,
driver boards ES841
Unipolar
cable, 1mm
2
Inverter module
U
ES841 MR1-3 Inverter
module
V
ES841 MR1-1
0VD power supply,
driver boards ES841
Unipolar
cable, 1mm
2
24V-GV
Inverter module
U
ES841 MR1-4 Inverter
module
V
ES841 MR1-2
+24VD power supply,
driver boards ES841
Unipolar
cable, 1mm
2
Inverter module
V
ES841 MR1-3 Inverter
module
W
ES841 MR1-1
0VD power supply,
driver boards ES841
Unipolar
cable, 1mm
2
24V-GW
Inverter module
V
ES841 MR1-4 Inverter
module
W
ES841 MR1-2
IGBT command,
Inverter module U
Double optical
fibre
G-U
Control unit
ES842 OP19-OP20 Inverter module U ES841
OP4-OP5
IGBT command,
Inverter module V
Double optical
fibre
G-V
Control unit
ES842 OP13-OP14 Inverter module V ES841
OP4-OP5
IGBT command,
Inverter module W
Double optical
fibre
G-W
Control unit
ES842
OP8-OP9
Inverter module W ES841
OP4-OP5
IGBT fault, Inverter
module U
Single optical
fibre
FA-U
Control unit
ES842
OP15
Inverter module U ES841
OP3
IGBT fault, Inverter
module U
Single optical
fibre
FA-V
Control unit
ES842
OP10
Inverter module V ES841
OP3
IGBT fault, Inverter
module U
Single optical
fibre
FA-W
Control unit
ES842
OP5
Inverter module W ES841
OP3
Bus bar voltage
reading
Single optical
fibre
VB
Control unit
ES842
OP2
One Inverter
module
ES843 OP2
IGBT status, Inverter
module U
Single optical
fibre
ST-U
Control unit
ES842
OP16
Inverter module U ES843
OP1
IGBT status, Inverter
module V
Single optical
fibre
ST-V
Control unit
ES842
OP11
Inverter module V ES843
OP1
IGBT status, Inverter
module W
Single optical
fibre
ST-W
Control unit
ES842
OP6
Inverter module W ES843
OP1
CAUTION
Carefully check that connections are correct. Wrong connections can adversely
affect the equipment operation.
CAUTION
NEVER supply the equipment if optical fibre connectors are disconnected.
Содержание SINUS K
Страница 49: ...SINUS K INSTALLATION INSTRUCTIONS 49 191 S65 T S R U V W S64 Figure 8 Installation Example of a SINUS K S64 S65...
Страница 157: ...SINUS K INSTALLATION INSTRUCTIONS 157 191 Figure 75 Mechanical features of an AC 3 phase inductance...
Страница 186: ...INSTALLATION SINUS K INSTRUCTIONS 186 191 15 DECLARATIONS OF CONFORMITY...
Страница 187: ...SINUS K INSTALLATION INSTRUCTIONS 187 191...
Страница 188: ...INSTALLATION SINUS K INSTRUCTIONS 188 191...
Страница 189: ...SINUS K INSTALLATION INSTRUCTIONS 189 191...
Страница 190: ...INSTALLATION SINUS K INSTRUCTIONS 190 191...
Страница 191: ...SINUS K INSTALLATION INSTRUCTIONS 191 191...