Control method
IFD – LIFT = Space vector modulation (vectorial modulation PWM with V/f curve)
VTC = Vector Torque Control (Sensorless vectorial, direct torque control)
Frequency/speed setting
resolution
Digital reference: 0.1Hz (IFD SW); 1 rpm (VTC SW)
Analog reference 10bit: 0.01% resolution of maximum output
frequency/speed with respect to max. speed
Speed precision
Open loop: 0.5% of max. speed (2% for IFD SW and LIFT)
Closed loop (with encoder): < 0.5% of max. speed
Overload capacity
Up to 2 times rated current for 120sec.
Starting torque
Up to 200% Cn for 120sec and 240% Cn for a short duration
CONTROL
Torque boost
Programmable for a rated torque increase
Operation method
Operation through terminals, keypad, serial communication
Analog inputs
4 analog inputs:
2 voltage sum inputs, resolution 10bits
1 current input, resolution 10bits
1 voltage input, resolution 10bits
Analog: 0÷10VDC, +/-10VDC, 0 (4) ÷20mA.
Digital: from keypad, serial communication
Digital inputs
8 NPN/PNP digital inputs: 3 fixed inputs (ENABLE, START, RESET) and 5
programmable inputs
Multi frequency/
Multispeed
IFD: 15 programmable frequency sets +/-800Hz
VTC: 7 programmable speed sets +/-9000rpm
LIFT: 4 programmable speed sets 0÷2.5m/sec
Input signals
Ramps
4 + 4 accel./decel. ramps, 0 to 6500sec; possibility to set user-defined curves.
Digital outputs
3 configurable digital outputs with setting of internal timers for
activation/deactivation delay:
2 relay outputs with reverse contacts 250VCA, 30VDC, 3A
1 open collector output, NPN/PNP 5÷48VDC, 50mA max
Auxiliary voltage
24VDC +/-5%, 100mA
Potentiometer voltage
+10Vdc –0% + 2%, 10mA
OPERATION
Output si
gna
ls
Analog outputs
2 configurable analog outputs, 0÷10VDC and 0(4)÷20mA, 8bits resolution
Alarms
Inverter thermal protection, motor thermal protection, mains failure,
overvoltage, undervoltage, overcurrent at constant speed or ground failure,
overcurrent while accelerating, overcurrent while decelerating, overcurrent
during speed search (IFD SW only), auxiliary trip from digital input, serial
communication failure, Eeprom failure, control board failure, precharge
circuit failure, inverter overload conditions for long duration, unconnected
motor, encoder failure (VTC SW only), overspeed (VTC SW only).
PROTECTIONS
Warnings
INVERTER OK, INVERTER ALARM, acceleration – constant rpm -deceleration,
current/torque limiting, POWER DOWN, SPEED SEARCHING (IFD SW only),
DC braking, autotuning (VTC SW only).
Operating data
Frequency/torque/speed reference, output frequency, motor speed, required
torque, generated torque, current to motor, voltage to motor, bus DC
voltage, motor-absorbed power, digital input condition, digital output
condition, trip log (last 5 alarms), operating time, auxiliary analog input
value, PID reference, PID feedback, PID error value, PID regulator output, PID
feedback with programmable multiplying factor, (cage speed reference, cage
speed, cage acceleration time, length covered by the cage while accelerating,
cage deceleration time, length covered by the cage while accelerating) (*).
(*)LIFT SW only
Serial communication
Standard incorporated RS485 multidrop, up to 247 devices
MODBUS RTU communication protocol
COMMUNICA
TION DISPLAY
Field bus
AB Communicator: optional MODBUS/field bus converter (Profibus DP; Can
Bus; Device Net; Ethernet; etc.).
Each device may control up to 4 inverters.
SAFETY
EN 61800-5-1, EN50178, EN60204-1, IEC 22G/109/NP
MARK
Содержание SINUS K
Страница 49: ...SINUS K INSTALLATION INSTRUCTIONS 49 191 S65 T S R U V W S64 Figure 8 Installation Example of a SINUS K S64 S65...
Страница 157: ...SINUS K INSTALLATION INSTRUCTIONS 157 191 Figure 75 Mechanical features of an AC 3 phase inductance...
Страница 186: ...INSTALLATION SINUS K INSTRUCTIONS 186 191 15 DECLARATIONS OF CONFORMITY...
Страница 187: ...SINUS K INSTALLATION INSTRUCTIONS 187 191...
Страница 188: ...INSTALLATION SINUS K INSTRUCTIONS 188 191...
Страница 189: ...SINUS K INSTALLATION INSTRUCTIONS 189 191...
Страница 190: ...INSTALLATION SINUS K INSTRUCTIONS 190 191...
Страница 191: ...SINUS K INSTALLATION INSTRUCTIONS 191 191...