SINUS K
INSTALLATION
INSTRUCTIONS
127/
191
13.2.2.3.
I
NDICATOR
LED
S
The indicator LEDs below are located on the front part of the braking units:
OK LED
Normally “on”; the equipment is running smoothly.
This LED turns off due to overcurrent or power circuit failure.
B LED
Normally off”; this LED turns on when the braking unit activates.
TMAX LED
Normally “off”; this LED turns on when the thermoswitch located on the heatsink of the braking
unit trips; if overtemperature protection trips, the equipment is locked until temperature drops
below the alarm threshold.
Figure 56: Position of the indicator LEDs.
13.2.3.
R
ATINGS
INVERTER SUPPLY VOLTAGE and JUMPER POSITIONS
200-240Vac
(2T class)
380-480Vac
(4T class)
480-500Vac
(4T class)
J4 J3 J5
SIZE
Max. Braking
Current (A)
Average
Braking
Current (A)
MIN. BRAKING
RESISTOR (Ohm)
MIN. BRAKING
RESISTOR (Ohm)
MIN. BRAKING
RESISTOR (Ohm)
BU200
130 80
3
6
6
B LED
TMAX LED
OK LED
Содержание SINUS K
Страница 49: ...SINUS K INSTALLATION INSTRUCTIONS 49 191 S65 T S R U V W S64 Figure 8 Installation Example of a SINUS K S64 S65...
Страница 157: ...SINUS K INSTALLATION INSTRUCTIONS 157 191 Figure 75 Mechanical features of an AC 3 phase inductance...
Страница 186: ...INSTALLATION SINUS K INSTRUCTIONS 186 191 15 DECLARATIONS OF CONFORMITY...
Страница 187: ...SINUS K INSTALLATION INSTRUCTIONS 187 191...
Страница 188: ...INSTALLATION SINUS K INSTRUCTIONS 188 191...
Страница 189: ...SINUS K INSTALLATION INSTRUCTIONS 189 191...
Страница 190: ...INSTALLATION SINUS K INSTRUCTIONS 190 191...
Страница 191: ...SINUS K INSTALLATION INSTRUCTIONS 191 191...