SINUS K
INSTALLATION
INSTRUCTIONS
103/
191
12.3.
Communication Ratings
IFD
SW
Parameters
VTC SW
Parameters
Electrical standard:
RS485
Protocol: MODBUS
RTU
Supported functions:
03h (Read Holding Registers)
10h (Preset Multiple Registers)
Device address:
configurable between 1 and 247 (default
address: 1)
C90
C80
Inverter response delay:
configurable between 0 and 500 ms (default
delay time: 0 ms)
C91 C81
End of message timeout:
configurable between 0 and 2000 ms (default
timeout: 0 ms)
C93 C83
Baud rate:
configurable between 1200..9600 bps
(default baud rate: 9600 bps)
C94
C84
Data format:
8 bits
Start bit:
1
Parity/ Stop bit
Configurable among:
NO/2 stop bit (default value)
Even/ 1 stop bit
NO/ 1 stop bit
C95 C85