SINUS K
INSTALLATION
INSTRUCTIONS
11/
191
Do not connect supply voltages exceeding the equipment rated voltage to avoid
damaging the internal circuits.
If the inverter is installed in environments exposed to flammable and/or explosive
substances (zones AD according to standards IEC 64-2), please refer to IEC 64-2,
EN 60079-10 and related standards.
Do not connect the equipment power supply to the output terminals (U,V,W), to
the resistive braking unit terminals (+, -, B) and to the control terminals. The
equipment power supply must be connected only to terminals R,S,T.
Do not short-circuit terminals (+) and (-) and terminals (+) and (B); do not
connect any braking resistors with lower ratings than the required ratings.
Do not start or stop the motor using a contactor over the inverter power supply.
Do not install any contactor between the inverter and the motor. Do not connect
any power factor correction capacitor to the motor.
Do not install any contactor between the inverter and the motor. Do not connect
any power factor correction capacitor to the motor.
Operate the inverter only if a proper grounding is provided.
In case of alarm trip, a comprehensive review of the Diagnostic section in the
Programming Manual is recommended. Restart the equipment only after
removing the cause responsible of the alarm trip.
Do not perform any insulation test between the power terminals or the control
terminals.
Make sure that the fastening screws of the control terminal board and the power
terminal board are properly tightened.
Do not connect single-phase motors.
Always use a motor thermal protection (use the inverter motor thermal model or a
thermoswitch installed in the motor).
Respect the environmental requirements for the equipment installation.
The bearing surface of the inverter must be capable of withstanding high
temperatures (up to 90°C).
CAUTION
The inverter electronic boards contain components which may be affected by
electrostatic discharges. Do not touch them unless it is strictly necessary. Always
be very careful so as to prevent any damage caused by electrostatic discharges.
Содержание SINUS K
Страница 49: ...SINUS K INSTALLATION INSTRUCTIONS 49 191 S65 T S R U V W S64 Figure 8 Installation Example of a SINUS K S64 S65...
Страница 157: ...SINUS K INSTALLATION INSTRUCTIONS 157 191 Figure 75 Mechanical features of an AC 3 phase inductance...
Страница 186: ...INSTALLATION SINUS K INSTRUCTIONS 186 191 15 DECLARATIONS OF CONFORMITY...
Страница 187: ...SINUS K INSTALLATION INSTRUCTIONS 187 191...
Страница 188: ...INSTALLATION SINUS K INSTRUCTIONS 188 191...
Страница 189: ...SINUS K INSTALLATION INSTRUCTIONS 189 191...
Страница 190: ...INSTALLATION SINUS K INSTRUCTIONS 190 191...
Страница 191: ...SINUS K INSTALLATION INSTRUCTIONS 191 191...