INSTALLATION
SINUS K
INSTRUCTIONS
52/
191
7.7.
Through-panel Assembly and Fixing Points
(Stand-Alone Models S05-S50)
The through-panel assembly allows segregating the air flow cooling the power section in order to avoid
dissipating power due to inverter loss inside the inverter case. The inverters available for through-panel
assembly are from size S05 to S50, both IP20 and IP00. As a result, unless other features are included, IP44
rating becomes IP40.
7.7.1.
SINUS
K
S05
For this inverter size, the air flow of the power section is segregated from the air flow of the control section through the
installation of two optional mechanical parts to be assembled with five self-forming screws M4 (see Figure 11).
Figure 11: Mounting the accessories for the through-panel assembly of SINUS K S05.
The equipment height becomes 488 mm with the two additional components (see Figure 12)The figure also
shows the piercing template of the mounting panel, including four holes M4 for the inverter mounting and two
slots (142 x 76 mm and 142 x 46 mm) for the air-cooling of the power section.
Figure 12: Fixing points of the mounting panel for the through-panel assembly of SINUS K S05.
Содержание SINUS K
Страница 49: ...SINUS K INSTALLATION INSTRUCTIONS 49 191 S65 T S R U V W S64 Figure 8 Installation Example of a SINUS K S64 S65...
Страница 157: ...SINUS K INSTALLATION INSTRUCTIONS 157 191 Figure 75 Mechanical features of an AC 3 phase inductance...
Страница 186: ...INSTALLATION SINUS K INSTRUCTIONS 186 191 15 DECLARATIONS OF CONFORMITY...
Страница 187: ...SINUS K INSTALLATION INSTRUCTIONS 187 191...
Страница 188: ...INSTALLATION SINUS K INSTRUCTIONS 188 191...
Страница 189: ...SINUS K INSTALLATION INSTRUCTIONS 189 191...
Страница 190: ...INSTALLATION SINUS K INSTRUCTIONS 190 191...
Страница 191: ...SINUS K INSTALLATION INSTRUCTIONS 191 191...