SINUS K
INSTALLATION
INSTRUCTIONS
31/
191
6.3.
OPERATING TEMPERATURES BASED ON
APPLICATION CLASSES
The operating temperature of the inverters of the SINUS K series is maximum 40 °C at rated current and can
reach max. 50 °C if the operating current is reduced. The operating temperature of some SINUS K models can
even exceed 40 °C at rated current. The maximum operating temperatures based on the inverter size and
application class are detailed in the tables below.
NOTE
The tables in this section apply to operating current values equal to or lower than the
current rating stated in the relevant application sheet.
APPLICATION - 2T-4T CLASS
LIGHT STANDARD HEAVY STRONG
Size
SINUS K Model
Maximum operating temperature (°C)
0005 50
50
50
50
0007 50
50
50
50
0009 40
45
50
50
0011 40
40
45
50
0014 40
40
40
50
0015 50
50
50
50
0016 45
50
50
50
S05
0020 40
45
50
50
0016 45
45
50
50
0017 40
45
50
50
0020 40
40
50
50
0025 40
40
50
50
0030 40
40
45
50
S10
0035 40
40
40
50
0016 45
45
50
50
0017 40
45
50
50
0020 40
40
50
50
0023 50
50
50
50
0025 40
40
50
50
0030 40
40
45
50
0033 45
50
50
50
0034 40
45
50
50
0036 40
40
45
50
S12
0037 45
40
45
50
0038 45
45
50
50
0040 40
45
50
50
S15
0049 40
40
50
50
0060 45
45
50
50
0067 40
40
50
50
0074 45
45
50
50
S20
0086 40
40
50
50
0113 45
45
50
50
0129 40
45
50
50
0150 45
45
50
50
S30
0162 40
40
50
50
(continued)
Содержание SINUS K
Страница 49: ...SINUS K INSTALLATION INSTRUCTIONS 49 191 S65 T S R U V W S64 Figure 8 Installation Example of a SINUS K S64 S65...
Страница 157: ...SINUS K INSTALLATION INSTRUCTIONS 157 191 Figure 75 Mechanical features of an AC 3 phase inductance...
Страница 186: ...INSTALLATION SINUS K INSTRUCTIONS 186 191 15 DECLARATIONS OF CONFORMITY...
Страница 187: ...SINUS K INSTALLATION INSTRUCTIONS 187 191...
Страница 188: ...INSTALLATION SINUS K INSTRUCTIONS 188 191...
Страница 189: ...SINUS K INSTALLATION INSTRUCTIONS 189 191...
Страница 190: ...INSTALLATION SINUS K INSTRUCTIONS 190 191...
Страница 191: ...SINUS K INSTALLATION INSTRUCTIONS 191 191...