background image

below the visible part of the screen, there will be a down arrow. If there are more rows above the
visible part of the screen, there will be an arrow pointing upwards.

Settings   display  with   parameter   change   -  

After   entering   this   screen,   a   blue   marker   frame   is

displayed   on   the   first   parameter.   You   can   use   the   arrows   to   position   the   marker  frame   on   the
parameter you want to edit. 
Then,   pressing   the   Enter   button   enters   the   edit   mode   for   this   parameter.   Then   the   blue   frame
becomes red, indicating that the parameter can be changed with the up and down buttons. Pressing
Enter again confirms the parameter change and exits the edit mode. If you want to edit another
parameter, you need to re-position it and then edit it by the same procedure.
When all the necessary adjustments to the parameters in the selected menu are made, pressing the
On-Off / Back button goes to the previous screen. 

Setting display with selection field.  

When any parameter requires only to be turned on or off, a

selection   field   is   used.   In   order   to   change   this   field,   it   is   sufficient   for   the   marker   frame   to   be
positioned on it. There, this frame becomes red and pressing the Enter button checks or unchecks
the selected parameter. When all the necessary adjustments to the parameters in the selected menu
are made, pressing the On-Off / Back button goes to the previous screen.

WARNING! 

If you do not change anything for a longer period (between 20 seconds and 5 minutes

depending on the setup menu), it will automatically exit the selected menu without saving the settings
made in this menu. The only exception is "

Temperature Setup

" menu, where changes made are

saved! 

WORKING WITH THE CONTROLLER
General information

The controller is managed by easy and intuitive software specifically designed to automate boiler
management.
When the water heater is switched on, he selects by itself the most suitable heat source. Priority is
given to using the solar collector (NHPC-V4-2 only) and the heat pump. The electric heater will only
be used if the heat pump is deactivated or if the set temperature is above the heating capabilities of
the heat pump. It will also be switched on if "

Enhanced Heating

" mode is used.

If the differential temperature associated with the solar collector  

Dt1 = t3 - t1

  is greater than the

threshold   set   in   the   “

Pump

 

Control”  

menu,   item   "

Solar   Dt1

",   column   "

On

",   the   solar   collector

circulation pump will be switched on in order to transfer its heat to the water heater. When the solar
pump is switched on but the differential temperature Dt1 drops below the threshold set on the same
row in the "

Off

" column, the pump will shut off.

25

Содержание HPWH 120

Страница 1: ...HEAT PUMP WATER HEATER 120 and 150 intended for wall mounting TECHNICAL DESCRIPTION INSTALLATION USE AND MAINTENANCE INSTRUCTIONS v20190723...

Страница 2: ...kage into the atmosphere ATTENTION The connection of the indoor unit with a built in heat exchanger to the heat supply system solar and or other water heating systems using water or an aqueous solutio...

Страница 3: ...and thus heats water Energy is extracted directly from the air A small amount of electricity is required to operate the compressor Heat pumps are made up of two parts an outdoor unit with a compresso...

Страница 4: ...r tanks of the appliances are suitably protected against corrosion by means of a high quality enamel coating or high alloy chromium nickel steel Enamelled water tanks incorporate special alloy anodes...

Страница 5: ...on of the installation and the connection of the heat exchanger of the water heater to it shall be performed only by qualified and competent companies with such subject of activity and in accordance w...

Страница 6: ...he wall with the most suitable position with enough space to simplify the installation and maintenance of the outdoor unit Figure 1 b The outdoor unit shall be installed on a load bearing wall or non...

Страница 7: ...e the shortest and as simple as possible way max 8 m long and 3 m elevation gain WARNING This is one of the conditions for the validity of the warranty d Protect pipes and cables to prevent damage ATT...

Страница 8: ...system e Place the insulation on the pipes as first closing their openings in order to prevent any contamination getting inside them f Place the brass nuts on the pipes in the correct direction and m...

Страница 9: ...1 4 Approximately 150 200 kgcm 15 20 Nm 9 52 mm 3 4 Approximately 350 400 kgcm 35 40 Nm Fig 8 CONNECTING OF THE REFRIGERANT PIPES WITH THE OUTDOOR UNIT Remove the protective plastic cover from the ou...

Страница 10: ...age with a suitable detector Fig 11 CONNECTING OF THE INDOOR UNIT TO THE PLUMBING INSTALLATION Fig 12 The plumbing installation to which the indoor unit will be connected as well as the other elements...

Страница 11: ...indoor unit to the plumbing system its water tank must be filled with water This is done in the following order Opethn the hot water tap on the farthest mixing cock Open the shut off valve 4 of Figur...

Страница 12: ...y the company that has designed the project for installation and connecting the indoor unit It is imperative to install all equipment provided and or recommended by it in regard to safety control and...

Страница 13: ...re the protective earth conductor if the cord is released from its attachment After connecting the appliance to the electrical system it is necessary to check its functionality WARNING Failure to comp...

Страница 14: ...r 2 upper 15 Indoor unit 16 Magnesium anode 17 Thermal switch 18 Communication cable to the outdoor unit 19 Heater 20 Power supply of the appliance 21 Flange bracket 22 Wi Fi module optional 23 Solar...

Страница 15: ...sconnected terminals The power supply cable to the UPS is connected to the terminals Lout phase and Nout zero The output of the UPS is connected to the terminals Lin phase and Nin zero WARNING It is i...

Страница 16: ...el coating should not be removed but only wiped with dry cotton cloth without the use of rigid tools Regular removal and cleaning of limestone is essential for the reliability of the appliance It is d...

Страница 17: ...special valve is integrated in the combined valve which in normal operation of the indoor unit allows the water expanded during its heating not to drip through the side opening of the valve but to en...

Страница 18: ...es 8 Information field 9 Air temperature around the heat pump 10 Heat pump When the heat pump is switched on the blade moves Main screen appliances with heat exchanger 1 Additional features of the boi...

Страница 19: ...f the solar If the solar thermal sensor does not work the solar circulation pump will be switched on continuously to avoid overheating of the solar installation Vacation The boiler is in a manually ac...

Страница 20: ...the graphs with the average water temperature at the top of the boiler The first three types of graphics are for the last 4 days and the average temperature graphs are for the last 2 days These chart...

Страница 21: ...inlet temperature 3 Position of EEV 4 Supply voltage 5 Current 6 Power Consumption 7 Evaporator temperature 8 External ambient temperature 9 Heat pump condition 10 Compressor condition 11 Fan conditio...

Страница 22: ...ng the day Vacation Mode Freeze protection solar Activated mode for protection of the solar panel against freezing Freeze protection boiler Activated mode for protection of the boiler against freezing...

Страница 23: ...t Damaged Flash A malfunction of the microcontroller resulting in the failure to record the settings in the non volatile memory i e changes to settings are lost when power supply is lost Update Outdoo...

Страница 24: ...red The heat pump stops working until the voltage has reached the allowable range High current Current exceeds 7 5A The heat pump stops but can be switched on again after the compressor re start prote...

Страница 25: ...all the necessary adjustments to the parameters in the selected menu are made pressing the On Off Back button goes to the previous screen WARNING If you do not change anything for a longer period bet...

Страница 26: ...p will switch on regardless of the differential temperature The pump will shut off if the water temperature in the water heater exceeds 85 C Overheating protection at the top of the boiler If the temp...

Страница 27: ...when the desired temperature can not be achieved with other heat sources for example at a set temperature above the heat pump maximum allowable or if there is another problem with the heat pump operat...

Страница 28: ...by the heat pump and the electric heater The set temperature adjustment ranges are from 20 to 75 C When setting a temperature that exceeds the heat pump allowance the heating is done only with the ele...

Страница 29: ...t reduction in electricity costs a low temperature can be set from the Temperature Setting and only in the required time intervals via the timer to switch on the heat pump forcedly and or the electric...

Страница 30: ...ghtness of the display Field Anode will define the presence of Anode Protection if the boiler is made of stainless steel there is no anode protection The Power field adjusts the power of the power hea...

Страница 31: ...nterrupted its clock is maintained for up to 24 hours If the power is turned off for an extended period of time the clock stops and the next time it is turned on it must be reset WARRANTY WARRANTY TER...

Страница 32: ...hange of the shape dimensions and location of parts and components that are exposed to an impact which is not in accordance with its normal use Lost profits tangible and intangible damages caused by t...

Отзывы: