background image

DISMANTLING THE BURNER TRAY

Remove the tray as previously described. The pilot unit can be removed by undoing the tubing
nut, the thermocouple nut on the rear of the valve, lint arrestor, two securing screws, and lifting
away. Remove the tubing nut from the valve end of the pilot pipe, and blow through to dislodge
any debris that may be present. Clean the exterior of the pilot assembly with a soft brush and
blow through the flame ports on the pilot head. Check the aeration holes are free from lint or dirt.
The pilot assembly is a non-serviceable item, and should not be taken apart. The aeration hole
must be absolutely clear internally for proper operation. A thoroughly cleaned (inside and out)
oxypilot will cure a wide range of ignition faults. 
Remove the two tubing nuts on the ends of the gas pipe to the injector elbow. Release the screw
through the  supporting leg and lift assembly clear. The injector pipe can now be checked for
debris. Remove the nut retaining the injector elbow. Blow through the elbow to remove any
debris.
The valve is not field serviceable, apart from the pilot filter. Remove the control knob by pulling
it forwards, then remove the largest of the three screws on the face of the valve. Slide the filter
out and clean away any debris that may have accumulated. The filter element should also be
blown clean. This component should not require replacement, however if signs of deterioration
are evident then a genuine spare must be used. If a large amount of debris is present in the fil-
ter then the pipework and control should be thoroughly cleaned before re-assembly.

TROUBLESHOOTING GUIDE

Fire sparks but pilot does not light

No gas to fire, check isolators are open.
Pipework blockage, clean out.
Air not fully purged, re-purge supply or wait longer.
Spark earthing to metal work, reset gap correctly.
Blocked pilot, clean out internally.

Pilot lights but then goes out

Severe restriction in gas supply, clear obstruction.
Faulty thermocouple, replace pilot unit.
Hold control knob in for longer.

Fire does not spark at pilot

HT lead detached, refit.
Spark gap too large or small, reset correctly.
Faulty piezo unit, replace.
Debris shorting out electrode, clean.

Fire runs for a time and then cuts off

Excessive room draught or flue pull, rectify.
Loose or faulty thermocouple, rectify.
ODS system in operation.
Firebox grommet seal not fitted, rectify.
Lint in pilot aeration hole, clean thoroughly internally

Pilot flame shrinks 

Poor gas flow to fire, check pressure with fire on high.

when fire is on high

If pressure is low, remove any restriction in pipework or valve.
Check all isolators are adequately sized and fully open.
Check meter pressure is adequate.
Air leak under base of firebox, rectify.
Lint in pilot aeration hole, clean thoroughly internally.

Fire smells when first lit or in use

Newness smell from brand new appliance.
Spillage occurring. Carry out spillage test and rectify any problems.
Low temperature sealants or combustible materials used in
incorrect positions.

9

19.0

18.2

©

2009 Focal Point Fires plc.

Содержание eko 2050

Страница 1: ...installation and user instructions All instructions must be handed to user for safekeeping Revision A 06 09 Country s of destination GB IE eko 2050 fuel effect gas fire...

Страница 2: ...tible hearth of at least 300mm depth This appliance is factory set for operation on the gas type and at the pressure stated on the appliance data plate This appliance is a manual control version with...

Страница 3: ...Gas Safety Installation and Use Regulations 1998 the relevant British Standards for Installation Codes of Practice and in accordance with the Manufacturers Instructions The installation shall also be...

Страница 4: ...flue must be connected to only one fireplace and the flue must not vent more than one appli ance i e not shared with a gas back boiler There must be no opening in the flue apart from the one that the...

Страница 5: ...75mm 7in minimum diameter twin wall flue conforming to BS 715 Any existing under grate draught device must be sealed off The opening wall must be non combustible The appliance requires a hearth with n...

Страница 6: ...in these circumstances may be the best solu tion Any ventilation fitted must comply with BS 5871 part 2 and BS 5440 part 2 Ventilation locat ed underneath or within the immediate vicinity of the fire...

Страница 7: ...fire box to prevent the ingress of dirt and dust Using 8mm diameter pipe connect the appliance to the gas supply point The appliance must be fitted with rigid or semi rigid pipe of 8mm external diamet...

Страница 8: ...tion The main burner will light and be controlled in accordance with the main burner control knob set ting Adjust the main burner control knob to the desired setting If the pilot is extinguished durin...

Страница 9: ...this If a grommet seal has been left out of the firebox if fitted then this also will also cause inter mittent shutdown The gas pressure reaching the fire must also be checked The thermocouple connec...

Страница 10: ...the coals or ceramics or wash them in water SERVICING Ensure that the fire is fully cold before attempting service A suggested procedure for servicing is detailed below 1 Lay out the dust sheet and t...

Страница 11: ...are evident then a genuine spare must be used If a large amount of debris is present in the fil ter then the pipework and control should be thoroughly cleaned before re assembly TROUBLESHOOTING GUIDE...

Страница 12: ...tion for further details on clearances to combustibles No combustible material or flooring should protrude onto the hearth DO NOT burn any foreign material on this fire the fuel effect must be of the...

Страница 13: ...ormally required for this appliance The requirements of other appliances operating in the same space or room and the results of a spillage test must be taken into consideration when assessing ventilat...

Страница 14: ...behind the second row of coals in order to complete the third row The coals may be orientated as desired to achieve a realistic effect Keep the spacing between the coals even and uniform The two coals...

Страница 15: ...of the fuel bed The pebbles may be orien tated as desired to achieve a realistic effect Keep the spacing between the pebbles even and uni form 5 Finally take the four remaining pebbles and place at t...

Страница 16: ...aining two medium sized logs numbered 5 and 7 and place in a horizontal position shown 5 first resting on the front log strip 7 next resting on 5 Now take the smallest log numbered 12 and position in...

Страница 17: ...ner will light and be controlled in accordance with the main burner control knob set ting Adjust the main burner control knob to the desired setting If the pilot is extinguished during use of the fire...

Страница 18: ...ion in the installation guide of these instructions Do not create dust from the coals Clean gently in the open air Replace components with original spares only as necessary SERVICING The fire and flue...

Отзывы: