background image

SETTING PRESSURE

Remove the screw from the pressure test point. 
The pressure test point is situated on the main injector
pipe next to the pilot.

The setting pressure should be in accordance with the
figures stated on page 2 of these instructions. The fire
is factory set to achieve these pressures, and any signif-
icant variation could indicate a supply problem.

If the pressure is too high, the gas supply meter may be
set incorrectly. This should be checked with the fire running and if necessary reset by the gas sup-
plier.

If the pressure is too low, then check the meter governor pressure with the appliance running. If
this is incorrect it will need to be reset by the gas supplier. If the setting pressure is too low, but
the meter pressure is acceptable, then a problem in the supply pipework is to be suspected. This
will be dirt and debris, kinked or inadequate size pipes, restriction in a fitting or solder flashing
across a joint. (NOTE: you will not get an accurate reading of the inlet pressure with a pressure
gauge on the end of the supply pipe - this is the static pressure in the system. You must use a T
piece and measure the supply pressure with the fire on High - the dynamic pressure). Refit and
tighten the screw into the pressure test point when the test is complete.

FLUE SPILLAGE MONITORING SYSTEM

This fire is fitted with a flue spillage safety device (ODS). If the fire shuts down during use for no
apparent reason then several things may be suspected. If a door or window has been opened cre-
ating a draught, then pilot disturbance is the problem, and removal of the draught should resolve
this. If a grommet seal has been left out of the firebox (if fitted) then this also will also cause inter-
mittent shutdown. The gas pressure reaching the fire must also be checked. The thermocouple
connection into the back of the gas control valve may also have worked loose during installation,
simply tighten to remedy if this is the case.

If pilot disturbance is not the cause, then the ODS safety system may be in operation. Switch the
appliance OFF, check the flue and carry out any remedial work required. Re-light the fire and carry
out a spillage test. DO NOT allow the appliance to be used if it continues to fail a spillage test.
The aeration hole of the pilot must be carefully cleaned out on each annual service to ensure con-
tinued function of the ODS.
The spillage monitoring system shall not be adjusted, modified, or put out of operation by the
installer. Any spare parts fitted MUST be of a type supplied for the purpose by the appliance man-
ufacturer.

If the fire is not spilling, then further guidance should be sought, using the Troubleshooting sec-
tion as a guide.

TESTING FOR SPILLAGE

Close all doors and windows to the room containing the appliance. Let the fire run on HIGH for
five minutes. Take a smoke match, light it, and using a smoke match tube, hold it at the top edge
of the fire opening, 25mm down and 25mm in. Starting 50mm in from either side, run the smoke
match across the opening. 

7

14.0

15.0

16.0

A.25mm down from

top of opening

B. 25mm in from

front of opening.

C. Disregard outer

50mm either side of

fireplace opening

Match

Crimp

Tube

Cross section of smoke match tube

Make a smoke match tube from 10mm diameter
tube. Seal off one end and crimp the tube to prevent
the smoke match from sliding down inside.

C

C

B

A

Fireplace Opening

Smoke Match In

Tube

©

2009 Focal Point Fires plc.

Содержание eko 2050

Страница 1: ...installation and user instructions All instructions must be handed to user for safekeeping Revision A 06 09 Country s of destination GB IE eko 2050 fuel effect gas fire...

Страница 2: ...tible hearth of at least 300mm depth This appliance is factory set for operation on the gas type and at the pressure stated on the appliance data plate This appliance is a manual control version with...

Страница 3: ...Gas Safety Installation and Use Regulations 1998 the relevant British Standards for Installation Codes of Practice and in accordance with the Manufacturers Instructions The installation shall also be...

Страница 4: ...flue must be connected to only one fireplace and the flue must not vent more than one appli ance i e not shared with a gas back boiler There must be no opening in the flue apart from the one that the...

Страница 5: ...75mm 7in minimum diameter twin wall flue conforming to BS 715 Any existing under grate draught device must be sealed off The opening wall must be non combustible The appliance requires a hearth with n...

Страница 6: ...in these circumstances may be the best solu tion Any ventilation fitted must comply with BS 5871 part 2 and BS 5440 part 2 Ventilation locat ed underneath or within the immediate vicinity of the fire...

Страница 7: ...fire box to prevent the ingress of dirt and dust Using 8mm diameter pipe connect the appliance to the gas supply point The appliance must be fitted with rigid or semi rigid pipe of 8mm external diamet...

Страница 8: ...tion The main burner will light and be controlled in accordance with the main burner control knob set ting Adjust the main burner control knob to the desired setting If the pilot is extinguished durin...

Страница 9: ...this If a grommet seal has been left out of the firebox if fitted then this also will also cause inter mittent shutdown The gas pressure reaching the fire must also be checked The thermocouple connec...

Страница 10: ...the coals or ceramics or wash them in water SERVICING Ensure that the fire is fully cold before attempting service A suggested procedure for servicing is detailed below 1 Lay out the dust sheet and t...

Страница 11: ...are evident then a genuine spare must be used If a large amount of debris is present in the fil ter then the pipework and control should be thoroughly cleaned before re assembly TROUBLESHOOTING GUIDE...

Страница 12: ...tion for further details on clearances to combustibles No combustible material or flooring should protrude onto the hearth DO NOT burn any foreign material on this fire the fuel effect must be of the...

Страница 13: ...ormally required for this appliance The requirements of other appliances operating in the same space or room and the results of a spillage test must be taken into consideration when assessing ventilat...

Страница 14: ...behind the second row of coals in order to complete the third row The coals may be orientated as desired to achieve a realistic effect Keep the spacing between the coals even and uniform The two coals...

Страница 15: ...of the fuel bed The pebbles may be orien tated as desired to achieve a realistic effect Keep the spacing between the pebbles even and uni form 5 Finally take the four remaining pebbles and place at t...

Страница 16: ...aining two medium sized logs numbered 5 and 7 and place in a horizontal position shown 5 first resting on the front log strip 7 next resting on 5 Now take the smallest log numbered 12 and position in...

Страница 17: ...ner will light and be controlled in accordance with the main burner control knob set ting Adjust the main burner control knob to the desired setting If the pilot is extinguished during use of the fire...

Страница 18: ...ion in the installation guide of these instructions Do not create dust from the coals Clean gently in the open air Replace components with original spares only as necessary SERVICING The fire and flue...

Отзывы: