INSTALLATION REQUIREMENTS

This appliance MUST NOT be installed into a room containing a bath or shower, or where steam
may be  present. The fire has been designed to fit into a builders’ opening or fireplace conform-
ing to BS 1251 (and meeting certain dimensional requirements), or a suitable flue box complying
with the constructional requirements of BS 715. Either a ‘Replacement Chairbrick’ or a BS 1251
chairbrick should also be fitted into the builders’ opening. The flue box must be installed onto a
suitable non-combustible insulating surface at least 12mm thick, covering the entire base are of
the box.

The flue must have an effective height of at least three meters, as measured from the hearth to
the top of the flue. Any flue damper plates or restrictors should be removed and no other restric-
tion fitted to the flue. Where removal is not practical, the restriction must be fixed in the fully
open position.

A natural draught flue system is required, and if previously used for solid fuel or oil burning, the
flue and chimney must be swept prior to appliance installation. The flue must be checked before
installation by using a smoke pellet or similar to ensure proper draw and that leakage is not evi-
dent at any joints. Repair and re-test as necessary before the appliance is installed.

The flue must be connected to only one fireplace, and the flue must not vent more than one appli-
ance (i.e. not shared with a gas back boiler). There must be no opening in the flue apart from the
one that the appliance is installed into, and the one venting the gases into the air. A suitable ter-
minal may be fitted, such as class GC1, as regulations allow.

This appliance has been tested for use with circular flues of a minimum internal diameter of
175mm.

The flue termination (cowl) must be of a type suitable for use with an inset Decorative Fuel Effect
Fire BS5871 part 3 contains further details.

2

2.0

3.0

APPLIANCE DATA

Manual control models                            Remote control models

Gas Group

G20 Natural Gas CAT I2H

G20 Natural Gas CAT I2H

Inlet Pressure

20 mbar  (+/- 2.0mbar)

20 mbar  (+/- 2.0mbar)

Max Energy Input (gross)

6.8 kW

6.8 kW

Min Energy Input (gross)

3.5 kW

3.5 kW

Pilot Energy Input (gross)

166 W

166 W

Setting Pressure (cold)

15.8 mbar (+/- 1.5mbar)

 

15.8 mbar (+/- 1.5mbar)

Main Injector Burner

Stereo size 81/Bray cat. 82/420

Stereo size 81/Bray cat. 82/420

Gas Inlet Connection

8mm Inlet Restrictor Elbow

8mm Inlet Restrictor Elbow

Gas Control Valve

Dungs BM 733/NGC 6801

Mertik Maxitrol GV30 series

Ignition

Integral Piezo spark

Integral Piezo spark

Spark Gap

3.5 to 4.5mm

3.5 to 4.5mm

Weight

20 Kg

20 Kg

Please see Data Badge affixed to appliance for current data.

This appliance is for use only with the gas type, and at the pressure stated on the appli-

ance Data Badge, and is for decorative purposes.

©

2009 Focal Point Fires plc.

Содержание eko 2050

Страница 1: ...installation and user instructions All instructions must be handed to user for safekeeping Revision A 06 09 Country s of destination GB IE eko 2050 fuel effect gas fire...

Страница 2: ...tible hearth of at least 300mm depth This appliance is factory set for operation on the gas type and at the pressure stated on the appliance data plate This appliance is a manual control version with...

Страница 3: ...Gas Safety Installation and Use Regulations 1998 the relevant British Standards for Installation Codes of Practice and in accordance with the Manufacturers Instructions The installation shall also be...

Страница 4: ...flue must be connected to only one fireplace and the flue must not vent more than one appli ance i e not shared with a gas back boiler There must be no opening in the flue apart from the one that the...

Страница 5: ...75mm 7in minimum diameter twin wall flue conforming to BS 715 Any existing under grate draught device must be sealed off The opening wall must be non combustible The appliance requires a hearth with n...

Страница 6: ...in these circumstances may be the best solu tion Any ventilation fitted must comply with BS 5871 part 2 and BS 5440 part 2 Ventilation locat ed underneath or within the immediate vicinity of the fire...

Страница 7: ...fire box to prevent the ingress of dirt and dust Using 8mm diameter pipe connect the appliance to the gas supply point The appliance must be fitted with rigid or semi rigid pipe of 8mm external diamet...

Страница 8: ...tion The main burner will light and be controlled in accordance with the main burner control knob set ting Adjust the main burner control knob to the desired setting If the pilot is extinguished durin...

Страница 9: ...this If a grommet seal has been left out of the firebox if fitted then this also will also cause inter mittent shutdown The gas pressure reaching the fire must also be checked The thermocouple connec...

Страница 10: ...the coals or ceramics or wash them in water SERVICING Ensure that the fire is fully cold before attempting service A suggested procedure for servicing is detailed below 1 Lay out the dust sheet and t...

Страница 11: ...are evident then a genuine spare must be used If a large amount of debris is present in the fil ter then the pipework and control should be thoroughly cleaned before re assembly TROUBLESHOOTING GUIDE...

Страница 12: ...tion for further details on clearances to combustibles No combustible material or flooring should protrude onto the hearth DO NOT burn any foreign material on this fire the fuel effect must be of the...

Страница 13: ...ormally required for this appliance The requirements of other appliances operating in the same space or room and the results of a spillage test must be taken into consideration when assessing ventilat...

Страница 14: ...behind the second row of coals in order to complete the third row The coals may be orientated as desired to achieve a realistic effect Keep the spacing between the coals even and uniform The two coals...

Страница 15: ...of the fuel bed The pebbles may be orien tated as desired to achieve a realistic effect Keep the spacing between the pebbles even and uni form 5 Finally take the four remaining pebbles and place at t...

Страница 16: ...aining two medium sized logs numbered 5 and 7 and place in a horizontal position shown 5 first resting on the front log strip 7 next resting on 5 Now take the smallest log numbered 12 and position in...

Страница 17: ...ner will light and be controlled in accordance with the main burner control knob set ting Adjust the main burner control knob to the desired setting If the pilot is extinguished during use of the fire...

Страница 18: ...ion in the installation guide of these instructions Do not create dust from the coals Clean gently in the open air Replace components with original spares only as necessary SERVICING The fire and flue...

Отзывы: