DATE: 24AUG00
INSTALLATION SHEET:
INSTALLATION SHEET P/N: 387132
REVISION LEVEL: 4.0
FILE NAME: 387132.CDR
CREATED BY: B. Graham
APPROVED BY: M. Slack
DL2 Dialer Module
Digital Alarm Communicator Transmitter
PRODUCT DESCRIPTION
INSTALLATION
PRODUCT DIAGRAM
The DL2 is a dialer module, which contains a Digital Alarm Communicator
Transmitter (DACT). The dialer sends alarm, supervisory, and trouble
information to a compatible Digital Alarm Communicator Receiver (DACR)
through one or two dial-up telephone lines (two per NFPA 72). The dialer
supports 20 PPS 4/2 format and Dual Tone Multi-Frequency (DTMF) or
Pulse mode dialing. E
he dialer performs an automatic test
call to verify communications between the fire alarm panel and the Central
Monitoring Station (CMS).
very 24 hours, t
SPECIFICATIONS
Input power
Mounting
Phone line
Wall connector
Line supervision
Communications protocol
CMS telephone numbers
FCC registration number
Dialing retries
Clock accuracy
Compliance
Programming phone
Environmental conditions
Supervisory
10 mA
Active
20 mA
Mounts on the Main Controller Module
One/two loop start lines on public
switched telephone network, pulse or
DTMF dialing. Party, ground start, and
PBX start lines are not acceptable. NFPA
72 requires two phone lines.
Standard RJ31X or RJ38X phone jack
Trouble when line voltage less than 10 V
and line current less than 5 mA.
SIA pulse format 20 PPS 4/2 double
round, 1400 Hz handshake, 1900 Hz
carrier
Two 24-digit numbers
4Z2USA-22549-AL-E
five to ten
Within one hour/year
Communications Canada, CS-03;
FCC/CFR 47 parts 15 and 68; NFPA 72;
UL 864; ULC S527-M87
Any tone dial phone with an RJ11 plug
Temperature range
32 to 120 °F (0 to 49 °C)
Humidity range
0 to 93%, non-condensing
Carefully match mounting holes up with spacers to ensure proper
connector mating.
1
Install three metal spacers (P/N 362329)
in the three locations indicated below.
2
Mount the DL2 on the three metal spacers.
3
Mate connector P1 on the DL2 with connector JE on the Main
Controller Module.
4
Secure the DL2 to the spacers with the screws provided.
with the screws provided
Mounting the DL2
JE
Main Controller Module
DL2
4-40X
Metal
spacer
4-40X
5/16
panhead
screw
JE
P1
P1
Main Controller Module
Dialer
Disconnect external ac power and battery power to cabinets before
installing or removing components. Failure to do so may result in
serious injury or loss of life.
Warning!
Caution!
!
Observe static-sensitive material handling practices.
Dialer codes
Event
Code
Fire alarm report codes
01-32
Fire alarm restore codes
41-72
Normal 24 hr check-in
90
Abnormal 24 hr check-in
91
Supervisory alarm
92
Trouble
93
94
AC power fail
96
Battery trouble
97
Telephone line trouble
98
Dialer disabled
99
Trouble / supervisory restore
Install metal
spacers here.
EDWARDS SYSTEMS TECHNOLOGY, INC.
SARASOTA, FL: 941-739-4300 FAX 941-753-1806
CHESHIRE, CT: 203-699-3000 FAX 203-699-3075
OWEN SOUND, CANADA: 519-376-2430 FAX 519-376-7258
INTERNATIONAL, CANADA: 905-270-1711 FAX 905-270-9553
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание EST2
Страница 18: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 22: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 24: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 28: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 58: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 64: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 66: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 80: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 88: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 90: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 92: ...Technical Manuals Online http www tech man com firealarmresources com ...