P/N: 387345 REV: 2.0 Page 2 of 2
DIP SWITCH SETTINGS
WIRING
S1
S3
S2
S4
J1
JP1
J4
ON
1
2
3
4
Function
S1-1
S1-2
S1-3
S1-4
Slow whoop
off
off
off
off
Fast Whoop
ON
off
off
off
1 kHz steady
1 kHz march time
ON
ON
off
off
1 kHz Morse U
off
off
ON
off
Hi-Lo
off
off
ON
off
Chime
off
ON
ON
off
Horn
ON
ON
ON
off
Low tone
off
off
off
ON
Hi-Lo Horn
ON
off
off
ON
Fast Hi-Lo Horn
off
ON
off
ON
Temporal
ON
ON
off
ON
4-4 code
off
off
ON
ON
1 kHz @ 20 bpm
ON
off
ON
ON
1 kHz @ 120 bpm
off
ON
ON
ON
off
ON
off
off
Function
S3-1
S3-2
S3-3
S3-4
Slow whoop
off
off
off
off
Fast Whoop
ON
off
off
off
1 kHz steady
1 kHz march time
ON
ON
off
off
1 kHz Morse U
off
off
ON
off
Hi-Lo
off
off
ON
off
Chime
off
ON
ON
off
Horn
ON
ON
ON
off
Low tone
off
off
off
ON
Hi-Lo Horn
ON
off
off
ON
Fast Hi-Lo Horn
off
ON
off
ON
Temporal
ON
ON
off
ON
4-4 code
off
off
ON
ON
1 kHz @ 20 bpm
ON
off
ON
ON
1 kHz @ 120 bpm
off
ON
ON
ON
off
ON
off
off
Function
S2-1
S2-2
S2-3
S2-4
Zone 23 and 24 enable
ON
X
X
X
Mode 0
X
X
off
off
Mode 1
X
off
ON
off
Mode 2
X
off
off
ON
Mode 3
X
off
ON
ON
Mode 4
X
ON
off
off
Function
S4-1
S4-2
S4-3
S4-4
Channel 1 and 2 modes
Mode 0
X
X
off
off
Mode 2
X
off
off
ON
Mode 3
X
off
ON
ON
Mode 4
X
ON
off
off
Mode 5
ON
X
X
X
Mode 6 (Ch 2 only)
X
off
ON
off
Channel 1: Evac signals
Channel 2: Alert signals
Channel 1: Evac operating modes
Channel 2: Alert operating modes
J2
J3
Channel 1 audio output
(47 k
resistor required for Class B wiring)
W
Channel 2 audio output
(47 k
resistor required for Class B wiring)
W
Channel 1 audio return
(Class A only)
Channel 2 audio return
(Class A only)
+
+
+
+
+
+
_
_
_
_
_
_
TB2
TB1
TB3
TB4
Data in
AUX. input 1 AUX. input 2
Data out
See the 2-TEL
installation sheet
See the 2-MIC
installation sheet
2-AAC
All wiring is supervised and power-limited.
Shields shall be continuous and isolated from
ground, except at the orignating panel.
1
2
Notes
Ribbon cable to Main Controller Module
or Expander Loop Module
Ribbon cable to
additional modules
An X indicates that the switch does not apply to the mode.
DS1
Mode
Description
0
1
2
3
4
5
6
Zone 23
Zone 24
Tones selected by S1 and S3 are available at TB1 and TB3 upon activation of the Audio Control
Module.
Boston code sequence (Evac channel only).
The signals connected to the auxiliary input terminals (TB4) are available at the output terminals
(TB1 and TB3) upon activation of the Audio Control Module.
Silence for five minutes on fire.
The pre-announce tone disables the microphone and sounds the horn tone for five seconds
upon the activation of the push-to-talk (PTT) switch.
Supervisory tone on TB3 and TB4 when the Audio Control Module is inactive.
Disables the generation of trouble conditions for applications without a microphone.
Generated upon the activation of
the Evac circuit (Ch 1, TB2)
whenever an operator pushes the Phone to Evac or Page to Evac switch at the 2-MIC.
the Audio Control Module and
Generated upon the activation of the Audio Control Module and the Alert circuit (Ch 2, TB3)
whenever an operator pushes the Phone to Alert or Page to Alert switch at the 2-MIC.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание EST2
Страница 18: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 22: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 24: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 28: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 58: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 64: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 66: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 80: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 88: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 90: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 92: ...Technical Manuals Online http www tech man com firealarmresources com ...