P/N: 387208 REV: 2.0 Page 2 of 2
S1
Group number
Output addresses S1 dip switch settings
Module
1
2
3
4
1
01-08
on
off
off
off
2-SANCOM
2
09-16
off
on
off
off
SHO-4
3
17-24
on
on
off
off
SDR-32(K)
4
25-32
off
off
on
off
SDR-32(K)
5
33-40
on
off
on
off
SDR-32(K)
6
41-48
off
on
on
off
SDR-32(K)
7
49-56
on
on
on
off
8
57-64
off
off
off
on
9
65-72
on
off
off
on
10
73-80
off
on
off
on
11
81-88
on
on
off
on
12
89-96
off
off
on
on
ON 1
2
3
4
To set the dip switches:
A.
Configure the SAN-CPU in the system programming utility.
B.
Note the
in the programming utility
(09 to 65).
C.
Set the dip switches on S1 to the group number of the
SDR-32(K)’s start output address.
start output address of the SDR-32(K)
Set the SDR-32(K) dip switches.
3
Remember that the SDR-32(K):
Cannot occupy the 2-SANCOM addresses (01 through 09).
Requires four output address groups, which consist of eight
addresses each.
INSTALLATION
FIELD WIRING
In this example,
start
address is 17 and
the dip switches are
set to a binary 3.
the
SIN-16 does not
require any output
addresses. The
SDR-32(K)
S1
SDR-32(K)
1
17
9
25
P01
SDR-32(K)
P03
P02
P04
8
24
16
32
External device
power supply
External device
power supply
+
+
_
_
SDR-32K EXR
relay connection
SDR32K Auxiliary
relay connection
Resistor value to be sized for 100 mA
maximum current per output
To SAN-CPU
24 Vdc power in (-) terminal
All wiring is power-limited.
Nonsupervised connection
Connect the
power supply to the SAN-CPU
power input
terminal.
(-) terminal of the external device
(-)
SDR-32K LED connections
SDR-32 LED connections
Notes
1
2
2
2
3
3
!
Cautions
Observe static-sensitive material handling
practices.
Use some current limiting for the incandescent
lamps. Momentary current surges can exceed the
100 mA rating on the switching transistor and cause
permanent damage.
Make the ribbon cable connections.
2
JP1
P1
P1
P1
P1
P2
P2
P2
P2
2-SANCOM
From P1
on the
SAN-CPU
SIN-16
SDR-32(K)
SHO-4
A.
Plug the ribbon cable assembly (P/N 250080) from P1 of the SAN-CPU into P2 of the 2-SANCOM.
B.
Plug the ribbon cable from P1 of the 2-SANCOM to P2 of the next SAN series module.
C.
Plug the ribbon cable from P1 of each SAN module to P2 of the next SAN module until you reach the last one.
D.
Install the continuity jumper on the last SAN module.
Note: If the SDR-32(K)
is the last module,
install the continuity
jumper on JP1.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание EST2
Страница 18: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 22: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 24: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 28: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 58: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 64: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 66: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 80: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 88: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 90: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 92: ...Technical Manuals Online http www tech man com firealarmresources com ...