P/N: 387207 REV: 2.0 Page 2 of 2
S1
Group number
Output addresses S1 dip switch settings
Module
1
2
3
4
1
01-08
on
off
off
off
2-SANCOM
2
09-16
off
on
off
off
SHO-4
3
17-24
on
on
off
off
SRU-8
4
25-32
off
off
on
off
SWU-8(/3)
5
33-40
on
off
on
off
SWU-(8/3)
6
41-48
off
on
on
off
7
49-56
on
on
on
off
8
57-64
off
off
off
on
9
65-72
on
off
off
on
10
73-80
off
on
off
on
11
81-88
on
on
off
on
12
89-96
off
off
on
on
ON 1
2
3
4
To set the dip switches:
A.
Configure the SAN-CPU in the system programming utility.
B.
Note the
in the programming utility (09
to 89).
C.
Set the dip switches on S1 to the group number of the SRU-8’s start output
address.
start output address of the SRU-8
Set the SRU-8 dip switches.
3
Remember that the SRU-8:
Cannot occupy the 2-SANCOM addresses (01 through 09).
Requires one output address group, which consists of eight
addresses.
INSTALLATION
FIELD WIRING
In this example, the
start address is 17
and the dip switches
are set to a binary 3.
S1
SRU-8
1
1
9
9
5
5
2
2
10
10
6
6
3
3
11
11
7
7
4
4
12
12
8
8
To the control circuit
24 Vdc, 4A max.
rated for pilot duty
TB1
TB2
K1
K5
K2
K6
K3
K7
K4
K8
NC
NO
COM
Typical layout for a
single pole double
throw (SPDT) relay
terminal
Detail
Terminal Relay
Description
TB1-1
K1
NC
TB1-2
K1
COM
TB1-3
K1
NO
TB1-4
K2
NC
TB1-5
K2
COM
TB1-6
K2
NO
TB1-7
K3
NC
TB1-8
K3
COM
TB1-9
K3
NO
TB1-10
K4
NC
TB1-11
K4
COM
TB1-12
K4
NO
Terminal Relay
Description
TB2-1
K5
NC
TB2-2
K5
COM
TB2-3
K5
NO
TB2-4
K6
NC
TB2-5
K6
COM
TB2-6
K6
NO
TB2-7
K7
NC
TB2-8
K7
COM
TB2-9
K7
NO
TB2-10
K8
NC
TB2-11
K8
COM
TB2-12
K8
NO
SRU-8 Relay Table
Note: Power-limited if the source is power-limited. If the source is
nonpower-limited, maintain a space of 1/4 inch from power-limited wiring.
Otherwise, use FPL, FPLP, FPLR, or an equivalent in accordance with
the National Electric Code.
Make the ribbon cable connections.
2
JP1
P1
P1
P1
P1
P2
P2
P2
P2
2-SANCOM
From P1
on the
SAN-CPU
SRU-8
SWU-8(/3)
SHO-4
A.
Plug the ribbon cable assembly (P/N 250080) from P1 of the SAN-CPU into P2 of the 2-SANCOM.
B.
Plug the ribbon cable from P1 of the 2-SANCOM to P2 of the next SAN series module.
C.
Plug the ribbon cable from P1 of each SAN module to P2 of the next SAN module until you reach the last one.
D.
Install the continuity jumper on the last SAN module.
Note: If the SIN-16 is
the last module,
install the continuity
jumper on JP1.
JP1
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Содержание EST2
Страница 18: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 22: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 24: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 28: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 58: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 64: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 66: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 80: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 88: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 90: ...Technical Manuals Online http www tech man com firealarmresources com ...
Страница 92: ...Technical Manuals Online http www tech man com firealarmresources com ...