DBL Operating Instructions / MPC4
Last updated: 03.12.2020
Page 20 of 26
6. Operation Mode / Status / Error Messages
Display
Meaning / Reasons
Correction
Ah LIMIT
Charging process stopped
after the predefined limiting
value (ampere hours [Ah])
has been exceeded.
-
Maybe the battery capacity was
adjusted to low in the setup?
Indication for complete charging of
the battery: Switch the limiting
value (Ah) given in the setup for
the
charging
process
approximately 20% higher than the
manufacturer is declaring for the
battery capacity
-
Were possibly parallel consumers
activated during the charging
process?
-
The battery might be defective?
CABLE COMP
Cable compensation mode is
activated.
-
See chapter 5.5.6 Device Menu
CELLCHECK
The cell test is running (only
with activated short-cell
detection)
-
See chapter 7 Short Cell Detection
- instructions for application
CHARGE
The DBL is in operation mode
battery charge.
-
Battery is charged
CONTACT
(flashing)
Automatic load detection is
activated (the DBL checks if a
battery or a resistive load is
connected).
-
Connect battery or load to the
charger
-
Check the connected consumers
on any errors (wrong kind of
battery or external voltage source)
-
As the case may be there is a
defective cable (check connection
to the load or battery)
DISCHARGED
The voltage of the connected
battery is below U
min
.
-
Check battery if it is defective?
-
Check the operation mode and the
starting voltage U
min
- see chapter
5.5.4 Charge Menu (parameters
for the CHARGEMODE)
EXT.STOP
Operation interrupted via the
Remote OFF signal line.
-
Detach GND connection at PIN 25
(Remote OFF)