Solution-8 Installation Manual

Page 27

Electronics Design & Manufacturing

 ISSUE401.DOC

Zone  Configurations

Locations 164 - 195

0

...

0

Each zone has four programming locations allocated to it. The first of these locations contains the character for
the zone option (1 to 12), the second of these locations contains the character for the zone type (0 to 3). The third
location contains the channel number for the alarm reporting and the fourth location contains the expansion code.

Example:

To program Zone 1 as a delay-1, lockout siren, lockout dialler : Enter '4' into location 164  and a '1' into location
165. To make Zone 1 report on channel one to a high speed receiver, program a '1' into location 166 and a '9' into
167.

Channel

The code entered in this location will determine on which channel alarms will be reported. For 3+1 or 4+1
formats this location has no effect.

Expansion

If you do not require alarm reports from a zone, program its expansion code to '0'.  The dialler will not be
triggered by alarms on a zone that has an expansion code of '0.' The zone will function normally otherwise.
In the 3+1 and 4+1 formats this location selects the actual code to be sent.
If you want the zone to report an alarm then you must specify a digit other than '0' (zero) for the expansion code.

When using HI-SPEED expanded format, program a '9' as the expansion code, this will ensure correct
transmissions.

If you are using 4+2 format, the expansion code will be sent first as the 10s digit and the channel number will
follow as the units digit.

Zone

Location

Default

Number

Number

Option

Type

Channel

Expansion

Zone 1

164 to 167

1

1

1

9

Zone 2

168 to 171

1

0

2

9

Zone 3

172 to 175

1

0

3

9

Zone 4

176 to 179

1

0

4

9

Zone 5

180 to 183

1

0

5

9

Zone 6

184 to 187

1

0

6

9

Zone 7

188 to 191

1

0

7

9

Zone 8

192 to 195

1

3

8

9

Note:

The Zone configuration table is presented on the previous page.

Содержание Solution 8

Страница 1: ...Solution 8 Installation Manual Issue 4 01...

Страница 2: ......

Страница 3: ...sign and Manufacturing Pty Limited Trademarks Throughout this document trademark names may have been used Rather than put a trademark symbol in every occurrence of a trademark name we state that we ar...

Страница 4: ...CONFIGURATION TABLE 16 OUTPUT CONFIGURATIONS 17 EVENT TYPES 17 EVENT TYPE DESCRIPTION 18 POLARITY CONFIGURATIONS 19 TIME 19 PROGRAMMING LOCATIONS 20 PRIMARY TELEPHONE NUMBER 20 SECONDARY TELEPHONE NUM...

Страница 5: ...TIONS 45 1 User Code Alteration Mode 45 2 Domestic Phone Number Change Mode 45 3 Alarm Memory Recall 45 4 Walk Test Mode 45 5 Toggle Remote Output State 45 6 Initiate a Modem Call 45 7 Toggle Day Alar...

Страница 6: ...NITIONS AND DESCRIPTIONS 49 OPTIONAL EQUIPMENT 50 EDMSAT CC914 51 SOLUTION PRINTER INTERFACE CC812 51 SERIAL PRINTER CABLE CC809 52 SOLUTION PROGRAMMER CC814 52 EDMSTU CS800 52 SOLUTION SYSTEM PROGRAM...

Страница 7: ...stem for your installation So that you can obtain the most from your unit we suggest that you take the time to read through this manual and familiarise yourself with the numerous outstanding operating...

Страница 8: ...installed in a bedroom and the indicators become annoying at night the console extinguish mode will automatically turn off all the indicators after sixty seconds The console indicators will illuminate...

Страница 9: ...alarm memory exists This condition needs to be corrected before access will be allowed This is achieved by arming and disarming the system in succession It should be noted that when in installer progr...

Страница 10: ...the system is Armed or Un armed Only when the Installers Program mode has been accessed will any numerals appear on the displays NOTE The system must be in a disarmed state with no flashing L E Ds in...

Страница 11: ...in the control panels memory Programming Option Bits When programming these locations you will notice that there are four alternatives per location You may select one two three or all of these alterna...

Страница 12: ...to be carried out on the Programming Key This test is non destructive and the data will remain intact after the test has been completed One long beep indicates that the Key has failed and three beeps...

Страница 13: ...198 199 Low Battery 0 0 Location 200 Open Report 0 Location 201 Close Report 0 Location 203 Alarm Restore 0 Location 204 Trouble Code 0 Location 205 Trouble Restore 0 Location 206 Bypass Code 0 Locati...

Страница 14: ...illuminated 0 AWAY This will put you at location 0 being the start location required 10 2 13 6 3 1 10 5 5 5 0 Example With auto step disabled decimal point extinguished 0 AWAY This will put you at lo...

Страница 15: ...d in locations 230 and 231 A delay zone when triggered will delay for the specified time before alarming NOTE If the EDMSAT is connected then the unique fire sound will not be heard unless there is an...

Страница 16: ...lockout siren 11 0 Stay mode lockout dialler 11 2 Stay mode lockout dialler 12 0 Stay mode lockout siren lockout dialler 12 2 Stay mode lockout siren lockout dialler Opt Typ Delay 1 Opt Typ 24 Hour 1...

Страница 17: ...tion of the output The time option can be set from as low as 200ms to as long as 51 seconds Event types 8 9 can only be triggered when the system is disarmed Event Types Event Code Function 0 EDMSAT o...

Страница 18: ...ecomes armed during and after exit time It will reset when the panel is next disarmed Type 2 System Stay This event triggers as soon as the panel is armed in the Stay mode It will reset when the panel...

Страница 19: ...stem is being disarmed using the duress feature or when any two buttons in the same horizontal plane are pressed simultaneously It will reset when the system is next armed Type 15 Remote Control This...

Страница 20: ...in an attempt to contact the monitoring station If unsuccessful the secondary number will then be called three times as well This procedure will be repeated only once again ie maximum of twelve call...

Страница 21: ...New Zealand decadic pulse dialling 4 Alternate between DTMF and Australian Decadic 5 Alternate between DTMF and New Zealand Decadic NOTE The alternating sequence is as follows DTMF Decadic DTMF Decadi...

Страница 22: ...ith checksum 5 4 2 Pulsed 6 4 2 Pulsed with checksum 7 4 1 Pulsed Universal 8 4 1 Pulsed Expanded 9 3 1 Pulsed Universal 10 3 1 Pulsed Expanded 11 Domestic 12 Basic Pager 13 Advanced Pager 14 4 2 Expr...

Страница 23: ...2 Franklin DCI Vertex Silent Knight FAST 20pps 2300Hz HS 3 1 3 2 4 1 4 2 Ademco 10pps 1400Hz HS 3 1 3 2 4 1 4 2 20pps 2300Hz HS 3 1 3 2 4 1 4 2 40pps 1400Hz HS 3 1 3 2 4 1 4 2 DTMF Hi Low Hs Expanded...

Страница 24: ...ber in location 55 thus allowing domestic format the ability to identify 15 different systems calling the same number Installer Code Locations 56 61 123400 This code can be four or six digits long and...

Страница 25: ...the system This can be helpful when you need to give a code to someone who is only allowed to arm but not disarm the system such as a cleaner or guest NOTE If 6 digit codes are required a 1 must be pr...

Страница 26: ...lockout siren 11 0 Stay mode lockout dialler 11 2 Stay mode lockout dialler 12 0 Stay mode lockout siren lockout dialler 12 2 Stay mode lockout siren lockout dialler Opt Typ Delay 1 Opt Typ 24 Hour 1...

Страница 27: ...is location has no effect Expansion If you do not require alarm reports from a zone program its expansion code to 0 The dialler will not be triggered by alarms on a zone that has an expansion code of...

Страница 28: ...Battery Locations 198 199 29 A low battery report will be sent when the systems battery voltage falls below 10 5 volts or when a Dynamic Battery test detects a low capacity battery Location 198 holds...

Страница 29: ...report will be sent only if a previous alarm had occurred This is an ideal feature for detecting if an alarm occurs as the premises are being opened Example High Speed Expanded 5678 u222 2222 2 3 1 Fo...

Страница 30: ...report as well as an opening and closing report every day Set the option and program the test report to be sent when the client is normally opened During the working week most commercial premises woul...

Страница 31: ...cation Example High Speed Expanded 5678 3555 5555 7 3 1 Format 678 AR 4 2 Format 5678 AR CH Trouble Code T Location 204 9 A trouble report will be sent at the end of exit time to indicate that one or...

Страница 32: ...em is next disarmed If Bypass restore is not programmed then it can be assumed when an opening report is transmitted All Bypassed zones are automatically cleared when the control panel is next disarme...

Страница 33: ...d with 0 then answering incoming calls is totally disabled irrespective of any programmed options V3 If Location 211 is programmed with the value 15 then Answering Machine bypass will be enabled This...

Страница 34: ...0 is allowed to arm the system 8 Instant zones to have Delay 2 when armed in Stay mode Six Digit Codes This option sets the maximum code length to six digits offering a larger number of code combinati...

Страница 35: ...ystem with zones unsealed When this option is not selected then all zones will have to be sealed before the user is allowed to arm the system This feature is ignored if the system is to be remotely ar...

Страница 36: ...o receive codes from previously locked out zones during siren time Allow horn speaker beeps for radio key operation This feature will enable horn speaker beeps only to be heard when the system is arme...

Страница 37: ...little as 1 hour or as long as 255 hours The resolution however is 1 to 0 hours which means that if you set the first test report time to five hours then the first test may come in any time from four...

Страница 38: ...hen only zone 1 will cause a Day Alarm This feature is turned on and off by keying in the Master code 7 AWAY If a zone has been programmed for Day Alarm it can be isolated in the normal way so as to n...

Страница 39: ...35 0000 Outputs consists of three items The first is the event type being the conditions required to trigger the output Secondly a configuration option which determines the polarity and operation of t...

Страница 40: ...eper Locations 248 251 5310 Console beeper configuration parameters are entered in these four locations Location Description 248 Event type 249 Event polarity 250 Time in 200ms intervals 251 Time in 3...

Страница 41: ...rammer if connected The first number will be displayed for two seconds and then a beep will be heard as the next number is displayed You may watch as all stored numbers are displayed before programmin...

Страница 42: ...er the programmed ring count the panel will answer the call The siren tone will again be heard as well as an alarm type indication beep The alarm type beeps will indicate whether a burglary or 24 hour...

Страница 43: ...hone number locations 00 15 It should also be noted that both formats transmit the last 3 digits of the client number making it possible to differentiate between transmissions when a number of alarms...

Страница 44: ...e transmission has come from client number 678 and that 2 new events have occurred As this format is similar to basic 3 2 format the actual event types are installation dependant For example the above...

Страница 45: ...eature enables the playback of the last ten events that have occurred to the system For a more detailed description please refer to the Solution 8 Operators Manual 4 Walk Test Mode Allows you to test...

Страница 46: ...rt time has now been set and subsequent test reports will be sent according to the time intervals programmed in locations 222 223 3 Alarm Memory Recall This feature enables the playback of the last te...

Страница 47: ...te a Modem Call This mode will force the panel to call the telephone number programmed in locations 32 to 47 and attempt to connect to the upload download computer V3 7 Toggle Day Alarm This code has...

Страница 48: ...telephone line is present The advantages of this are very obvious and having this facility will allow you to offer faster service to your clients The Solution 8 control panel will need to have a modem...

Страница 49: ...utputs have a common terminal which is positive 12 Volts and each output is capable of sinking a maximum of 400mA The outputs are protected by EDM s unique Integrated Protection System I P S This make...

Страница 50: ...f the zones and their response times are programmable via the system programming options EARTH This terminal should be connected to a solid earth point such as a cold water pipe or earth stake in orde...

Страница 51: ...data from the panel to the office where it can then be printed We have designed the interface to be flexible Both standard Centronics and the Serial TP10 printers can be used This means that many of y...

Страница 52: ...that holds all your control panel default configuration data The Programming Key can hold all your common configuration data such as monitoring station telephone numbers and zone reporting channels f...

Страница 53: ...multiple arm disarm sites The arm and disarm terminals can be used to directly interface to any access control system There may be a need to interface your security control panel to a card reader or a...

Страница 54: ......

Отзывы: