50
Screen Display
Explanation
Go to Page For
Troubleshooting
Low water cutoff sees no water.
Go to Page 56
Flue temperature sensor sees temperature
higher than 200°F.
Go to Page 57
Return water temperature sensor sees
temperature higher than 200°F.
Go to Page 58
Control board internal error. Power down then
power up boiler. If error repeatedly occurs
replace control module.
Replace Control
Module
Boiler is powered by three wires, hot, neutral
and ground. E44 displays when neutral wire is
not neutral.
Go to Page 58
Control board sees power supply frequency not
in range of 59 to 61 Hz.
Go to Page 59
Boiler power supply ground wire is not
grounded.
Go to Page 60
Control board internal error. Power down then
power up boiler. If error repeatedly occurs
replace control module.
Replace Control
Module
Supply temperature sensor is open. No
continuity.
Go to Page 60
Return water temperature sensor is open. No
continuity.
Go to Page 61
Flue temperature sensor is open. No
continuity.
Go to Page 62
Supply water temperature sensor is shorted.
'0' Ohm
Go to Page 62
Return water temperature sensor is shorted.
'0' Ohm
Go to Page 63
Flue temperature sensor is shorted. '0' Ohm
Go to Page 63
Reset button was pressed too many times.
Error Clears in 1-2
minutes
Fault detected in blower motor system.
Go to page 59
B l o c k i n g E r r o r
F l u e G a s E r r o r
E 39
13 - TROUBLE SHOOTING
P/N# 240008888, Rev. O [07/15/2015]
Содержание Dunkirk Helix DKVLT-050
Страница 48: ...48 13 TROUBLE SHOOTING P N 240008888 Rev O 07 15 2015...
Страница 52: ...52 13 TROUBLE SHOOTING P N 240008888 Rev O 07 15 2015...
Страница 54: ...54 13 TROUBLE SHOOTING P N 240008888 Rev O 07 15 2015...
Страница 66: ...66 14 2 Schematic Diagram of Ladder Form 050 075 100 MBH 14 WIRING DIAGRAM P N 240008888 Rev O 07 15 2015...
Страница 67: ...67 14 WIRING DIAGRAM 14 3 Connection Diagram 150 200 299 MBH P N 240008888 Rev O 07 15 2015...