Installation instructions

Gas fired condensing boilers

CGB-11 

Boiler

CGB-20 

Boiler

CGB-K-20  Combi boiler

CGB-24 

Boiler

CGB-K-24  Combi boiler

Art.-Nr. 3061344_201509         Subject to technical modifications

GB

Wolf GmbH · Postfach 1380 · 84048 Mainburg · Tel. 08751/74-0 · Fax 08751/741600 · Internet: www.wolf-heiztechnik.de

Summary of Contents for CGB-11

Page 1: ...ers CGB 11 Boiler CGB 20 Boiler CGB K 20 Combi boiler CGB 24 Boiler CGB K 24 Combi boiler Art Nr 3061344_201509 Subject to technical modifications GB Wolf GmbH Postfach 1380 84048 Mainburg Tel 08751 74 0 Fax 08751 741600 Internet www wolf heiztechnik de ...

Page 2: ...28 Limiting the maximum output 29 Selecting the pump stage 30 Testing the combustion parameters 31 CO2 settings 32 33 Commissioning report 34 Technical conversion options for gas fired condensing boiler CGB 35 Conversion of combi boilers to boilers with cylinder 36 Maintenance 37 51 Modulating pump class A 52 3 stage pump 53 Design information 54 67 Underfloor heating system 68 Technical maintenan...

Page 3: ...is in the ON position This brings a risk of electrocution which may result in injury or death The main supply terminals are live even when the ON OFF switch is in the OFF position Safetyinstructions areinstructionswithwhich you must comply exactly to prevent injury and material losses Fig Gas connection Escaping gas may cause poisoning or the risk of explosion Fig Terminal box Danger from electric...

Page 4: ...water central heating systems Institute of Gas Engineers Publication IGE UP 7 1998 Guide for gas installations in timber framed housing Important The appliance must be installed and serviced by a competent person as stated in the Gas Safety Installation and Use Regulations 1998 In IE the installation must be in accordance with the current edition of I S 813 Domestic Gas Installations the current B...

Page 5: ...Standards and regulations Open flue gas fired condensing boilers must only be installed in a room which complies with the appropriate ventilation requirements Other wise there is a risk of asphyxiation and poiso ning Read these installation and maintenance instructions before installing the boiler Also take the Technical Guide into consideration Poorly vented LPG tanks can lead to ignition problem...

Page 6: ...ture of 20 75 C Thesettingontheheatingwaterthermostatbecomesineffectivewhenthesystemisused in conjunction with a digital room thermostat or a weather compensated controller ON OFF switch The gas fired boiler is OFF in position 0 Reset A fault is reset by pressing the reset button which will also restart the system Pressing the reset button reactivates the system if there was no fault Illuminated r...

Page 7: ...e the circulation pump operates constantly factory setting or only in parallel with the burner activation run on time Summer mode Winter mode is deactivated by rotating the heating water temperature selector into po sition In other words the equipment will then operate in summer mode Summer mode central heating OFF means only DHW heating Frost protection for the central heating system and pump ant...

Page 8: ...bined with CSW 120 Fig Dimensions Fig Dimensions Fig Dimensions 200 440 154 144 640 281 32 344 654 40 54 Fig Connections 1 2 6 3 4 5 DHW flow Heating flow Heating return Heating return DHW return Condensate drain 190 855 48 393 270 420 790 440 344 810 1800 1950 ...

Page 9: ...Heating flow DHW connection on site DHW connection Gas connection Cold water inlet Cold water inlet on site Heating return Condensate drain Fig Dimensions 70 54 640 654 40 32 281 120 200 440 344 Fig Dimensions 190 855 48 393 200 120 10 73 165 35 162 min 400 758 281 22 14 1 2 3 4 5 6 7 8 ...

Page 10: ...ay diverter valve Heating return DHW flow Gas supply pipe Fan motor Gas fan Expansion vessel Gas air mixing chamber Inlet pipe Gas combination valve Heating circuit pump auto venting Overflow valve Heating flow DHW return TBV flow sensor Flue gas temperature limiter Gas restrictor Condensate siphon Limit thermostat only for CGB 24 ...

Page 11: ...on Gas supply pipe Fan motor Gas fan Expansion vessel Gas restrictor Inlet pipe Gas combination valve Heating circuit pump auto venting Overflow valve Flow sensor Cold water strainer with flow switch Heating flow Cold water inlet Condensate siphon Flue gas temperature limiter Gas air mixing chamber Limit thermostat TBV flow sensor Limit thermostat only for CGB K 24 Layout ...

Page 12: ...s e g fluoride chlorine or sulphur Such materials are contained in sprays solvents and cleaning agents Under the most un favourable conditions these may lead to corrosion even in the flue gas system During the boiler installation ensure that no contaminants e g drilling swarf enter the gas fired boiler otherwise faults may result Use the enclosed polystyrene cover NB Clearance between the boiler a...

Page 13: ...n for the installation of the gas fired boiler In your deliberations consider the flue gas outlet the lateral clearances towards walls and ceilings and any existing con nections for gas central heating DHW and electrics Mounting the boiler with a mounting bracket During the boiler installation ensure that the fixing componentsaresufficientlystrongtocarryitsweight Also consider the wall consistency...

Page 14: ...he supply lines Each of the elbows can be turned 360 for easy connection of the supply lines from any direction Fit the installation accessories Fig Panel for mounting on unfinished walls accessories for CGB K CGB with FSW 120 Fig Subsurface installation template Fig Panel for mounting on unfinished walls accessories Fig Connection panel for surface mounted version acces sories for Gas fired boile...

Page 15: ...h safety valve connection straight ver sion accessories Notes Heating circuit safety valve Install a safety valve with marking H max 3 bar Fig Heating circuit safety valve accessories Fig Cold water supply acc to DIN 1988 We recommend the installation of a maintenance valve into the cold water supply A tested and certified pressure reducer must be installed if the cold water supply pressure is abo...

Page 16: ...lime concentrating on the heat exchanger surface of an individual boiler If appropriate start with the screed drying program The ÖNORM H5195 1 specifies that a hardness level of 17 dH is not exceeded There is a risk of poisoning through flue gases being expelled if the appliance is operated with an empty siphon Therefore fill the siphon with water prior to commissioning Undo the siphon remove it a...

Page 17: ...ylinder 200 l solar buffer SEM or third party cylinder accessories Gas connection Laying the gas pipe as well as gas connections must only be carried out by a licensed gas fitter Close the gas shut off valve on the gas fired boiler to pressure test the gas pipe Cleanallresiduesfromtheheatingpipeworkandthe gas pipe prior to connecting the boiler particularly in older systems Prior to commissioning ...

Page 18: ...est ports must remain accessible to the relevant authorities even after fitting the ceiling bezels NB Fig Example Balanced flue system Forconcentricair fluepipes balancedfluesystems use only original Wolf components Please observe the technical information regarding balanced flue systems prior to installing the flue pipe or the ventilation air connection Different countries have different regulati...

Page 19: ...byalicensed electrical contractor Observe local regulations and those of the power supply company Terminal box The control regulating and safety equipment are fully wired and tested You only need to connect the power supply and the external accessories Mains electrical connection Connect the power supply permanently or with a safety plug no plug connection in protective areas 1 and 2 i e near a ba...

Page 20: ...ccesso ries Connection output A1 230 V AC 200 VA Insert the cable glands into the terminal box Insert and secure the connecting cable through the cable gland Connect the cable to terminals L1 N and The parameters for output A1 are described in the table on the following page Fig Connection output A1 Changing a fuse Isolatethecondensingboilerfromthepower supply prior to changing a fuse The ON OFF s...

Page 21: ...is activated when the cylinder is heated up 7 Ventilation damper Output A1 is activated before each burner start The burner will however only be enabled after input E1 has been closed Important In any case input E1 must also be programmed as Ventilation damper The feedback to input E1 must be made with a zero volt contact 24V Otherwise use an on site relay for potential separation 8 External venti...

Page 22: ... capability The following functions can be allocated to input E1 Code Explanation 0 No function Input E1 is not taken into consideration by the control unit 1 Room thermostat With open input E1 heating operation will be blocked summer mode independent of any digital Wolf control acces sories 2 Maximum thermostat or system pressure switch Optional connection for a maximum thermostat or system press...

Page 23: ... pump by one revolution but do not remove the cap Open all radiator valves Open all flow and return valves on the gas fired condensing boiler Fill the system to 1 5 bar pressure In operation the pressure gauge must indicate between 1 5 and 2 5 bar Start the gas fired condensing boiler set the heating water temperature selector into position 2 pump running illumi nated ring status display constantl...

Page 24: ...nsure that the boiler matches the type of available gas See the following table for permissible Wobbe index subject to gas type The initial start up and operation of the boiler as well as the user instruction must only be carried out by a qualified contractor Natural gas H 15 0 WS 11 4 15 2 kWh m 40 9 54 7 MJ m LPG P WS 20 2 24 3 kWh m 72 9 87 3 MJ m Table Wobbe index subject to type of gas Switch...

Page 25: ...interface or cascade When operating several boilers number of boilers 1 in conjunction with a cascade module set the eBUS address of each boiler in accordance with the table below BUS address setting Hold down the reset button after 5 seconds the corresponding flashing code will be displayed see table Select the corresponding address with the DHW temperature rotary selector Release the reset butto...

Page 26: ... r h side of the thermomanometer using a screwdriver Pivot the control unit out Release the plug at test nipple and vent the gas supply pipe Connect the differential pressure meter to at test port Connect against atmosphere Switch ON the ON OFF switch After starting the boiler check the supply pressure at the differential pressure gauge Fig Check the gas supply pressure Natural gas If the supply p...

Page 27: ... gas supply pressure Switch OFF the ON OFF switch Close the gas shut off valve Remove the differential pressure gauge and reseal the test port with its plug Open the gas shut off valve Check the test nipple for gas leaks Complete the enclosed notice and affix to the inside of the casing Close the boiler Fig Shut off valves Flow shut off valve Return shut off valve Gas shut off valve ...

Page 28: ... fan speed central heating Maximum fan speed in for central heating CGB 11 70 CGB 20 82 CGB 24 82 27 100 GB05 A09 Frost protection outside temperature With connected outside temperature sensor and insufficient temperature pump ON C 2 10 10 GB06 HG06 Heating circuit pump mode 0 Pump ON in winter mode 1 Pump ON when the burner is ON 0 0 1 GB07 HG07 Heating circuit pump run on time Heating circuit pu...

Page 29: ...60 C Settings for parameter GB04 with Wolf connection accessories with eBUS capability in Maximum output in kW 25 5 0 4 0 3 0 6 0 7 0 8 0 9 0 10 0 11 0 12 0 13 0 14 0 15 0 16 0 17 0 18 0 19 0 20 0 21 0 22 0 23 0 24 0 25 0 30 35 40 45 50 55 60 65 70 75 80 85 CGB 11 CGB 24 CGB 20 Table Output setting CGB 24 CGB K 24 Heating output kW 7 1 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Display value 30...

Page 30: ...itch Remove the cover lid Unlock the control unit housing and pivot it out At the switch select the required pump stage Fig Switching stages at the three stage heating circuit pump stage 1 stage 2 stage 3 Pump stage selector Fig Selector at the three stage heating circuit pump The following settings are recommended Ensurethattheswitchcorrectlyclicksintoplaceand does not remain in an intermediate p...

Page 31: ...r remove the test probe and close the test port Ensure the screws seal tightly Testing the flue gas parameters Flue gas can escape into the installation room if the test port is not sealed This results in a risk of asphyxiation Remove the screw from the l h test port Open the gas shut off valve Start the gas fired condensing boiler and turn the tempera ture selector to the emissions test symbol il...

Page 32: ...t the control unit lid down Unlock the casing lid with the l h and r h rotating locks Release the lower part of the casing lid and unhook at the top Remove the screw from the l h Flue gas test port Insert the test probe of the CO2 test equipment into the Flue gas test port Turn the temperature selector to the emissions test position illuminated status display ring flashes yellow Check the CO2 cont...

Page 33: ... casing lid and check the CO2 value with the boiler closed Duringtheinitialstart up theECemissionscanreach 200 ppm for the first hours as binding agents from the insulation combust Observe the CO emissions whilst making CO2 ad justments The gas combination valve is incorrectly adjusted if the CO value lies 200ppm when the CO2 value is correct In that case take the following steps Fully insert the ...

Page 34: ...on 7 Vented boiler and system 8 System pressure 1 5 2 5 bar 9 Entered type of gas and output onto label 10 Function test carried out 11 Flue gas test Gross flue gas temperature tA C Ventilation air temperature tL C Net flue gas temperature tA tL C Carbon dioxide content CO2 or oxygen content O2 Carbon monoxide content CO ppm 12 Casing fitted 13 System user trained tech docs handed over 14 Confirm ...

Page 35: ...ty cylinder 86 02 714 86 02 715 Central heating boiler Boiler with cylinder Combi boiler only CGB 20 Heiztherme 86 02 668 86 02 708 Boiler with cylinder Combi boiler Combi boiler only CGB 20 Boiler 86 02 668 86 02 708 Combi boiler Boiler with cylinder 86 02 708 1 Conversion to other gas types from tu CGB 11 CGB K 20 CGB K 24 Natural gas H LPG P 86 10 593 86 10 927 LPG P Natural gas H 86 10 592 56 ...

Page 36: ...Wolf acces sories with the blue plug which has become vacant Install the filled siphon After the conversion carry out a master reset with power connected Otherwise no heat demand can be recognised All parameters will then be reset to their factory settings Ifyouhavealreadymadechangestothecontrolunitparameters to match the control unit to your system then it is essential to make notes of these chan...

Page 37: ...is in the OFF position This indicates technical instructions which you must observe to prevent material losses and boiler malfunctions NB Fig Terminal box Danger from electric power Fig Ignition transformer high voltage ignition electrode combustion chamber Danger through live electrical components danger through hot components General notes Maintenance work must only be carried out by a qualified...

Page 38: ... the lower part of the casing lid and unhook at the top The mains terminals are live even when the ON OFF switch has been switched OFF Disconnect the system from the power supply Pivot the control unit lid down Switch OFF the boiler at the ON OFF switch Close the gas shut off valve rotating lock ...

Page 39: ...enance Lift the combustion chamber Pull out the locking clip Crack open the gas supply connection Pull the control hose off the mixing chamber Danger of burning Several components may be hot Let these cool down or wear gloves ...

Page 40: ...40 3061344_201509 Maintenance Fit the cleaning tray Pivot the combustion chamber out Pull the plug off the gas fan Pull the plugs off the ionisation and the ignition electrodes ...

Page 41: ...e Visual burner gasket check Lubricate the burner gasket with Wolf silicone grease or replace and lubricate Rotate the combustion chamber pot and remove down wards Remove the combustion chamber lid upwards Open the retaining tabs ...

Page 42: ...eck the expansion vessel inlet pressure and increase it if required to 0 75 bar The heating circuit must be at zero pressure Clean the condensate pan Clean the heat exchanger with a brush Versions with coated heat exchanger must only be cleaned with a plastic brush ...

Page 43: ...and lower combustion chamber gasket lubricate the new gaskets with silicone grease Lubricate the combustion chamber seat Replace the monitoring electrode Check and replace the ignition electrode if necessary Visual insulation check replace if broken ...

Page 44: ...ace the combustion chamber lid on the combustion chamber and secure with locking tabs Assembly Install the combustion chamber pot Push the plug back onto the gas fan Push the plugs back onto the ionisation and the ignition electrodes NB ...

Page 45: ... the combustion chamber down into the condensate pan Secure the locking clip Check the gas restrictor only CGB Boiler output Gas type Gas restrictor 11 kW E H Green 430 17 20 523 20 kW E H Orange 580 17 20 532 LPG Green 430 17 20 523 24 kW E H White 780 17 20 522 LPG Red 510 17 20 520 ...

Page 46: ...ance Check the balanced flue system Remove the cleaning container Clean the cold water strainer Shut off the cold water supply Checking the siphon If required clean and re fill Check for tight fit prevent flue gas from escaping ...

Page 47: ...47 3061344_201509 Maintenance Fig Non return valve CGW CGS If the DHW output is too low descale the DHW heat ex changer and the non return valve Reopen the cold water tap ...

Page 48: ...er Set the program selector to emissions test mode Switch the boiler OFF and close the test ports and hose nipples check for leaks Fit the casing Flue gas test Re adjust the CO2 content if required see next page Carrying out a ventilation test Check LAF for soundness if the CO2 value 0 2 Emissions test mode position ...

Page 49: ...ue gas temperature controller Art Nr 86 03 033 1 Sealing collar for test port Art Nr 39 03 143 1 Silicone grease 10 g tube Art Nr 86 02 264 1 Burner gasket Art Nr 39 03 121 1 Flow temperature sensor Art Nr 86 03 038 1 Flue gas temperature controller Art Nr 86 03 058 1 Flue gas temperature controller Art Nr 86 01 869 1 Ignition electrod Art Nr 86 03 061 1 Protective anode for enamelled cylinder Art...

Page 50: ...anode every two years on enamelled cylinders O O 14 Assemble the equipment 15 Clean and fill the siphon install and check for tight fit O O 16 Descale the DHW heat exchanger if required O O 17 Clean the DHW strainer O O 18 Check the expansion vessel in case of water loss O O 19 Open the gas supply valve and start the boiler 20 Gas soundness test O O 21 Flue gas soundness test O O 22 Check the igni...

Page 51: ...O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O C C C C C C C C C C C C C C C C C C Report item Report item Report item Report item Report item Report item ...

Page 52: ...oad The power consumption is reduced by the pump modulation In DHW mode The heating circuit pump will not modulate but operates con stantly with the selected DHW pump speed see table In standby mode The heating circuit pump operated with the selected Standby mode pump speed Factory settings Pump speed Boiler Heating mode DHW Standby Max Min CGB 11 56 27 56 20 CGB K 20 77 48 74 20 CGB K 24 82 48 90...

Page 53: ... getting properly warm i e reduced Create hydraulic balancing flow rate of hotter radiators During spring and autumn the required room temperature is not reached Increase set room temperature at controller e g from 20 to 25 C Selected room temp is not reached when outside temperatures are very low Select a steeper heating curve at the controller e g from 1 0 to 1 2 ...

Page 54: ...3x C83x C53x C33x IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII IIIII I I I I I I I I I I I I I I I I I I II II II I II II I II I I II I I I I I I I I I I I I I I I I I I I I I I II II I II II C33x C43x C83x C93x C33x B33 C13x ...

Page 55: ...wall balanced flue 30 C83x Concentric connection to a moisture resistant flue gas chimney and combustion air through an outside wall balanced flue Calculation to DIN EN 13384 MRC manufacturer C93x Vertical flue for duct installation DN 80 rigid flexible 2 m horizontal concentric connecting line 13 22 1 Available fan draught 90 Pa The maximum length corresponds to the total length from the applianc...

Page 56: ...es outside the boiler room inside a duct with a fire resistance of at least 90 min and in living space of low height with a resistance of at least 30 min Fire may spread if these instructions are not observed The following applies to gas fired boilers with a balanced flue above the roof where only the roof structure lies above the ceiling If fire resistance is required for the ceiling the pipes fo...

Page 57: ...ngs and gaskets Always arrange couplings against the condensate flow direction Install the balanced flue with a slope of at least 3 towards the gas fired condensing boiler Install spacer clamps to secure the location see installation example Connection to the balanced flue The calculated length of the balanced flue system or the flue is derived from the straight pipe length and the length of the p...

Page 58: ...not be longer than 2 m For horizontal air supply pipes a maximum length of 2 m is recommended Observe special requirements for flues that are not surrounded by combustion air acc to DVGW TRGI 2008and all locally applicable combustion orders Connection to a moisture resistant flue type C53 C83x for balanced flue operation Connection to a combustion air and flue system type C63x that is not tested t...

Page 59: ... 100 slide coupling if required 4 Balanced flue DN60 100 500 mm 1000 mm 2000 mm 5 Balanced flue vertical DN60 100 roof outlet for flat or pitched roofs L 1200 mm L 1200 mm 1700 mm 6 Universal tile for pitched roof 25 450 7 Flat roof collar 8 Bend 45 DN60 100 9 Inspection elbow DN60 100 10 Bend 87 DN60 100 11 Rose 12 Support rail 13 Support bend 87 DN60 to DN80 14 Spacers 15 Flue DN80 500 mm 1000 m...

Page 60: ...coupling if required 4 Balanced flu DN60 100 500 mm 1000 mm 2000 mm 9 Inspection elbow 10 Bend 87 DN60 100 11 Rose 12 Support rail 13 Support bend 87 DN60 auf DN80 14 Spacers 15 Flue DN80 500 mm 1000 mm 2000 mm 16 Duct cover with UV stabilised terminal 17 Spacer clip 18 Balanced flue horizontal incl cowl 19 Connection to a flue gas chimney B33 length 250 mm with air apertures 17 18 18 11 11 11 11 ...

Page 61: ...stallation balanced flue duct C33x 1 Gas fired condensing boiler 3 Separator DN60 100 slide coupling if required 4 Balanced flu DN60 100 500 mm 1000 mm 2000 mm 9 Inspection elbow 11 Rose 12 Support rail 13 Support bend 87 DN60 100 14 Spacers 16 Duct cover with UV stabilised terminal 17 Spacer clip NB Install the horizontal line with 3 slope towards the boiler ...

Page 62: ...himney draught Obtain the flue outlet from the chimney manufacturer if required to safeguard the connection conditions Supplementary installation instructions for balanced flue DN60 100 Flat roof Affix the ceiling outlet approx Ø 130 mm 7 to the roof cover Pitched roof At 6 observe the installation instructions on the cowl regarding roof pitches If an inspection aperture is required for the balanc...

Page 63: ... the installation Adaptor 2 is always required NB Design information Vertical concentric balanced flue C33x examples system DN80 125 2 2 2 3 3 8 8 4 4 4 9 9 3 5 5 10 4 5 11 S S 6 6 6 4 5 4 7 7 7 1 1 1 12 13 6 14 1 Gas fired condensing boiler 2 Adaptor from DN60 100 to DN80 125 3 Balanced flue incl inspection aperture DN 80 125 250 mm long 4 Balanced flue DN80 125 500 mm 1000 mm 2000 mm 5 Spacer cl...

Page 64: ...5 2 10 10 17 18 20 18 17 18 19 20 18 1 1 1 Horizontal balanced flue routing through a pitched roof Flue on an external wall where required C13 x C53x B33 Dormer 1 Gas fired condensing boiler 2 Adaptor from DN60 100 to DN80 125 3 Balanced flue incl inspection aperture DN80 125 250 mm long 4 Balanced flue DN80 125 500 mm 1000 mm 2000 mm 5 Spacer clip 10 Inspection elbow 87 DN80 125 11 Bend 87 DN80 1...

Page 65: ... DN 80 vertical 16 22 11 4 5 4 2 26 10 4 8 1 C33x Connection to a concentric balanced flue inside a duct example DN80 125 C33x Connection to the flue inside a duct C93x 1 Gas fired condensing boiler 2 Adaptor from DN60 100 to DN80 125 4 Balanced flue DN80 125 500 mm 1000 mm 2000 mm 5 Spacer clip 8 Separator slide coupling if required 10 Inspection elbow 87 DN80 125 11 Support bend 87 DN80 125 16 R...

Page 66: ...th a 3 slope towards the outside install the air inlet with a cowl permissible wind pressure at the air inlet 90 Pa The burner will not operate with higher wind pressure Eccentric balanced flue Maintain the following clearance between the internal duct wall and the flue for circular ducts 3 cm for rectangular ducts 2 cm Secondary ventilation Secondary ventilation 1 Gas fired condensing boiler 2 Ad...

Page 67: ...n piece 3 25 22 23 24 8 4 4 5 S S 10 16 4 Generally install the adaptor from LAF DN60 100 to DN80 125 2 vertically and always on the flue outlet of the gas condensing boiler Determine distance A Flue length 4 always 100 m longer than distance A Always trim the flue on the smooth side never on the coupling side Chamfer the flue after trimming 4 9 9 D istance A Offset 11 10 11 11 4 4 Distance A Dist...

Page 68: ...le volume of the diaphragm expansion vessel 20 greater than recommended by the relevant standard A diaphragm expansion vessel which is too small will result in an ingress of oxygen into the heating system and therefore lead to corrosion damage NB When using pipes which are impermeable to oxygen the un derfloor heating system can be directly connected to a heating system with a rated output of up t...

Page 69: ...gory I2H II2H3P II2H3P Types of connection 1 Marking x indicates that all flue pipe components are surrounded by combustion air Boiler Type 1 Operating mode To be connected to Open flue Balanced flue moisture resistant chimney balanced flue chimney balanced flue routing acc to Build Regs cert LAF moisture resistant flue CGB K B23 B33 C13x C33x C43x C53 C53x C83x C93x X X B33 C53 C83x C43x C13x2 C3...

Page 70: ...ge 1 2 3 4 o o o o o o MT 3 15 A F1 br bl gn ge sw ws rt gn ws gr rs br ge rt B1 Vorlauf fühler S1 TW Vorlauf ws ge gn br S3 TW Brenn kammer nur bei CGB 24 K 2 1 1 2 B 4 2 Durchflußsensor X11 2 Kombitherme Hall AF E1 eBUS 1 2 a b Netz Z A1 N N N L1 L1 L1 1 2 1 2 1 2 L1 N L1 N L1 N L1 N L1 N Wiring diagram Terminal box Power supply 230 V AC 50Hz Z External accessories 230 V AC A1 Programmable outpu...

Page 71: ... exchanger water content DHW throughput Minimum flow pressure Min flow press to EN625 Spec water flow rate D at T 30 K Max design pressure DHW temperature range 2 DHW heat exchanger corrosion protection C C bar Ltr l min bar l min bar C 75 90 3 0 1 3 75 90 3 0 1 3 75 90 3 0 1 3 2 0 6 5 0 2 1 0 9 4 10 40 60 stainless steel 75 90 3 0 1 3 75 90 3 0 1 3 2 0 8 0 0 2 1 0 13 0 10 40 60 stainless steel Ex...

Page 72: ...mmand Replace the gas combination valve 24 Gas fan fault The gas fan does not reach the required pre purging speed Check the gas fan supply cable and gas fan Press the reset button 25 Gas fan fault The gas fan does not reach the ignition speed Check the gas fan supply cable and gas fan Press the reset button 26 Gas fan fault The gas fan does not stop Check the gas fan supply cable and the gas fan ...

Page 73: ...al space heating energy efficiency ηs 92 92 92 Annual energy consumption for space heating QHE kWh 5652 10739 13043 Sound power level indoors LWA dB 50 49 52 Any specific precautions that shall be taken when the space heater is assembled installed or maintained See installation instruction See installation instruction See installation instruction Wolf GmbH Postfach 1380 D 84048 Mainburg Tel 49 875...

Page 74: ...r space heating QHE kWh 10739 13043 Annual fuel consumption for water heating AFC GJ 18 18 Seasonal space heating energy efficiency ηs 92 92 Seasonal water heating energy efficiency ηwh 82 82 Sound power level indoors LWA dB 49 52 Any specific precautions that shall be taken when the space heater is assembled installed or maintained See installation instruction See installation instruction Wolf Gm...

Page 75: ...xiliary electricity consumption in standby mode PSB kW 0 005 0 005 0 005 0 005 0 005 Seasonal space heating energy efficiency ns 92 92 92 92 92 Useful efficiency at rated heat output and high temperature regime n4 87 9 88 0 88 0 87 8 87 8 Useful efficiency at 30 of rated heat output and low temperature regime n1 97 3 96 7 96 7 96 7 96 7 Standby heat loss Pstby kW 0 049 0 049 0 049 0 048 0 048 Igni...

Page 76: ...equirements specified in the following documents 6 1 BImSchV 26 01 2010 DIN EN 297 10 2005 DIN EN 437 09 2009 DIN EN 483 06 2000 DIN EN 677 08 1998 DIN EN 625 10 1995 DIN EN 60335 1 02 2007 DIN EN 60335 2 102 04 2007 DIN EN 55014 1 06 2007 In accordance with the following Directives 90 396 EEC Gas Appliances Directive 2004 108 EC EMC Directive 2006 95 EC Low Voltage Directive 2009 125 EG ErP Direc...