4 - INSTALLATION PROCEDURE
Table 3 - MINIMUM CLEARANCE DIMENSIONS
Inches
(mm)
Top
6”
(152mm)
Rear
6”
(152mm)
Control Side
7”
(178mm)
Opposite Side
6”
(152mm)
Front
18”
(457mm)
Flue/Vent Connector
6”
(152mm)
Near Boiler Piping
2”
(51mm)
WARNING
Improper installation, adjustment, alteration,
service or maintenance could result in death or
serious injury
.
!
WARNING
Fire hazard. Do not install boiler on
combustible
fl
ooring or carpeting. Failure to
follow these instructions could result in death
or serious injury.
!
FOR INSTALLATION ON NON-COMBUSTIBLE
1.
FLOORS ONLY -
For installation on combustible
fl
ooring special base must be used. (See
Replacement Parts Section.)
Boiler can not be
installed on carpeting.
NOTE: Greater clearances for access should supersede fire
protection clearances.
* De
fi
nition of Alcove is three sided space with no
wall in front of boiler. ANSI standard for alcove is 18
inches from front of appliance to leading edge of side
walls as shown below.
Installation must conform to the requirements
1.
of the authority having jurisdiction or, in the
absence of such requirements, to the National
Fuel Gas Code, ANSI Z223.1/NFPA 54.
Where required by the authority having
2.
jurisdiction, the installation must conform to the
Standard for Controls and Safety Devices for
Automatically
fi
red Boilers, ANSI/ASME CSD-1.
Boiler series is classi
fi
ed as a Category I. Vent
3.
installation shall be in accordance with "Venting of
Equipment ," of the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 or applicable provisions of the
local building codes.
Boiler has met safe lighting and other
4.
performance criteria with the gas manifold and
control assembly on the boiler per the latest
revision of ANSI Z21.13/CGA 4.9.
Install boiler such that gas ignition system
5.
components are protected from water (dripping,
spraying, rain, etc.) during appliance operation
and service, (circulator replacement, condensate
trap, control replacement, etc.).
Locate boiler on level, solid base as near chimney
6.
as possible and centrally located with respect to
heat distribution system as practical.
Allow 24 inches (610mm ) at front and right side
7.
for servicing and cleaning.
When installed in utility room, door should be
8.
wide enough to allow largest boiler part to enter,
or to permit replacement of another appliance
such as water heater.