INSTALLATION AND USER INSTRUCTIONS

400L, 500L & 570L Indirect 

PREMIER PLUS

Russian Version on Page 17

Summary of Contents for PREMIER PLUS 400

Page 1: ...1 INSTALLATION AND USER INSTRUCTIONS 400L 500L 570L Indirect PREMIER PLUS Russian Version on Page 17 ...

Page 2: ...r Plus water heater MUST be fitted with a pressure relief valve rated at 8 bar FAILURE TO PROVIDE ADEQUATE PRESSURE RELIEF WILL INVALIDATE ANY GUARANTEE AND LEAD TO A DANGEROUS INSTALLATION 1 2 Where the inlet pressure exceeds 6 bar a pressure reducing valve set at max 6 bar should be fitted to the inlet supply to the heater This MUST NOT be fitted between the pressure relief valve and the water h...

Page 3: ... A B 1502 1802 832 1132 570L 1997 1336 Table 1 Dimensions Diagram 1 Dimensions 320 316 496 666 B C A COLD INLET PRIMARY FLOW PRIMARY RETURN T P VALVE SECONDARY RETURN THERMOSTATIC CONTROL BOILER 3kW IMMERSION 40 30 45 924 HOT OUTLET ...

Page 4: ... 610 685 Max mains pressure 1 6MPa 16 bar Max design pressure 0 8MPa 8 bar Operating pressure PRV set pressure 0 3MPa 3 bar Max primary pressure 1 0MPa 10 bar Expansion relief valve setting 0 8MPa 8 bar Immersion heater electrical rating 3 0kW 240V 2 8kW 230V T P Rating 90 C 10 bar Notes 1 At 3 bar inlet pressure 2 At a primary flow temperature 80 C 2 C 3 The primary coil should not be exposed to ...

Page 5: ... It must be sited between the heater and the check valve or security group see diagram 3 below 3 6 A sanitary circuit expansion vessel may be fitted to the cold water supply as shown in diagram 3 below to prevent wastage of expanded water A 35L expansion vessel is recommended for this range of cylinders 3 7 A re circulation circuit can be installed on the sanitary water circuit A connection is pro...

Page 6: ... 4 3 The water heater is fitted with a control thermostat suitable for the control of the sanitary water storage temperature This thermostat should be connected via the terminal block provided to the primary heating circuit controls See diagrams 5 and 6 page 6 for wiring information 4 4 The electrical cable should enter the terminal cover via one of the cable grips provided The outer sheath of the...

Page 7: ... ON DHW ON PROGRAMMER 1 2 3 M 1 2 3 M Ph N Ph N Ph N INDIRECT THERMOSTAT AND THERMAL CUT OUT 2 PORT ZONE VALVE DHW HEAT EXCHANGER ROOM THERMOSTAT 2 PORT ZONE VALVE PRIMARY CH CIRCUIT BOILER PUMP 2 x 2 PORT ZONE VALVE SYSTEM 1 2 3 4 5 6 7 8 9 10 ELECTRICAL SUPPLY WIRING CENTRE NOTE THE EARTH CONNECTIONS HAVE BEEN OMITTED FOR CLARITY ALL EARTH CONNECTIONS MUST BE LINKED BACK TO THE EARTH TERMINALS I...

Page 8: ...RTH CONNECTIONS MUST BE LINKED BACK TO THE EARTH TERMINALS IN THE WIRING CENTRE CV PUMP 1 2 3 L N L N DHW OFF 1 2 Ph N INDIRECT THERMOSTAT AND THERMAL CUT OUT ROOM THERMOSTAT 3 PORT VALVE HOT WATER PRIORITY BOILER 3 PORT VALVE SYSTEM HOT WATER PRIORITY 1 2 3 4 5 6 7 8 9 10 ELECTRICAL SUPPLY WIRING CENTRE NOTE THE EARTH CONNECTIONS HAVE BEEN OMITTED FOR CLARITY ALL EARTH CONNECTIONS MUST BE LINKED ...

Page 9: ...le pole isolating switch with a contact separation of at least 3mm in both poles 5 5 The immersion heater should be wired in accordance with diagram 10 page 9 The supply cable must be routed through the cable gland provided and the outer sheath of the cable firmly secured by tightening the screw on the cable gland Always replace the cover before operating 5 6 DO NOT operate the immersion heater un...

Page 10: ... Thermostat Earth Post Fused 13A double pole isolating switch 1 5mm 3 core HOFR sheathed cable 230V MONOPHASE Diagram 10 1 2 3 4 5 Thermal cut out reset button Temperature adjustment Customer earthing terminal Thermostat L N E Diagram 11 ...

Page 11: ...ustment range 1 to 5 represents a temperature range of 10o to 70o C DISCONNECT THE ELECTRICAL SUPPLY before making any adjustments 6 11 For heating by indirect heat exchanger switch on the electrical supply to the boiler and ensure the programmer is set to HOT WATER mode Check that any motorised valves or primary pumps are working and allow the water heater to heat The indirect control thermostat ...

Page 12: ...e the terminal cover and disconnect wiring from the immersion heater thermostat Remove the immersion heater thermostat by carefully pulling outwards from the immersion heater 8 4 Unscrew immersion heater NOTE over time the immersion heater seal may become stuck to the mating surface if the seal is damaged replace with new one 8 5 The loose scale in the base of the water heater can be removed by in...

Page 13: ... continues to operate at its optimum performance it should periodically be maintained in accordance with the instructions given under the sections headed MAINTENANCE 10 4 IMPORTANT NOTES TO THE USER Do not block or restrict the discharge from any safety valve fitted Do not tamper with any safety valve fitted Do not bypass the thermal cut outs in any circumstances If a fault is suspected contact a ...

Page 14: ...lidate your guarantee and may render the installation dangerous Description Part no 3kW Immersion heater 1 3 4 screw thread 95 602 030 3 4 Temperature pressure relief valve 95 605 103 13 ENVIRONMENTAL INFORMATION 13 1 This water heater is manufactured from many recyclable materials At the end of its useful life it should be disposed of at an approved Recycling Centre to realise the full environmen...

Page 15: ... product development is such that we reserve the right to change product specifications without notice We do however strive to ensure that all information in this leaflet is accurate at the time of publication Notes ...

Page 16: ...16 Baxi Heating UK Ltd Heatrae Sadia Heating Trading Division Hurricane Way Norwich NR6 6EA England www heatraesadia com A BDR Thermea company 36006191_issue_04 ...