SPILL SWITCH
(BLOCKED VENT SAFETY SHUTOFF)
Spill switch is manual reset disc thermostat with
fi
xed
setpoint (340°F (171°C)), and normally closed contacts.
It is located at relief opening of integral draft diverter.
In event of chimney or venting system blockage causing
products of combustion to spill out of relief opening,
spill switch disc heats up and spill switch contacts open,
shutting down
fl
ow of gas to main burners by removing
power to gas valve.
In event spill switch contacts open, reset button on
back of switch will pop up. Spill switch must be reset
manually, after switch has cooled off, by pushing reset
button down. Check venting system and chimney
for blockage when restoring system to operating
condition. DO NOT operate boiler without spill switch.
17 - EQUIPMENT AND OPTIONAL ACCESSORIES
ROLLOUT SWITCH
(FLAME ROLLOUT SAFETY SHUTOFF)
Rollout switch is temperature-sensitive fuse link
device. Located on boiler base just outside
fi
re box.
In event of heat exchanger
fl
ueway blockage causing
fl
ame to roll out of
fi
re box, fuse does not change in
appearance when blown.
If rollout switch blows, it must be replaced with
exact replacement. Check heat exchanger
fl
ueways
for blockage when restoring system to operating
condition. DO NOT operate system without rollout
switch.