Appendix A
Calibrate the Analog Output to 5.0V
Equipment Needed: Voltmeter
•
Set voltmeter to DC Voltage.
•
On J5, measure between Pin 1 (Orange) and Pin 5 (White).
•
Change thermostat mode to OFF.
•
Enter Advanced Command 35 01 and press ON/OFF.
•
Enter Advanced Command 36 36 and press ON/OFF.
•
This should cause your reading to go close to 5.0V.
•
Change the value of 36 36 up or down a few values so it reads close to 5.0V. If you have to raise it
more than 36 50 or lower than 36 25, then there is an issue. Contact engineering
•
Enter Advanced Command 35 00
•
Verify that in the OFF mode, output is approx. 0.0V.
EcoWave Featur ing EcoTouch IO&M Guide
Telkonet, Inc.
For Use w ith Fir mw ar e Ver sion 2.x
20800 Sw enson Dr ive, Suite 175
Appendix A
Waukesha, WI 53186
Revision 2
(800) 380-9640
Page 40
w w w .telkonet.com