EcoSource High Voltage Installation
Table 1-Wiring:
Pin
Label on Backplate
Function
1
R (Power)
12-277VAC power from HVAC, used to power the thermostat
2
C (Common)
AC Common
3
AUX (Auxiliary)
User defined
4
W1 (Heat) (Strip)
Heat call or strip heat call (depends on programming)
5
Switched Power 1 (W1/Y1)
Provides alternate power for W1 and Y1
6
Y1 (Cool) (Comp)
Cool/Compressor call
7
G (Fan)
Fan Call - Low speed
8
O (B) (G2) (Y2) (Changeover)
Multi-use - depends on programming and site requirements:
•
Changeover
•
2
nd
Stage Fan
•
2
nd
Stage Cooling
9
Switched Power 2
Provides alternate power for G, O, and W2
10
W2 (Y2) (G2) (G3) (Multi-speed)
Multi-use - depends on programming and site requirements:
•
2
nd
stage heat
•
Electric heat (for HPs with strip heat, etc.)
•
Emergency heat
Step 14
Carefully push the wired connections back into the JBOX.
Step 15
Mount pre-wired 16 gauge SS6000 backplate on top of JBOX adapter, using four #5 ½” coarse
thread screws. See Figure 8.
Figure 8: Backplate on Adapter Plate
Step 16
Ensure no airflow from JBOX or wall cavity is able to seep into the thermostat through the wire
harness. Telkonet recommends the use of UL caulk or UL rated insulating tape as shown in
Figure 9 to avoid false temperature readings.
EcoWave Featur ing EcoTouch IO&M Guide
Telkonet, Inc.
For Use w ith Fir mw ar e Ver sion 2.x
20800 Sw enson Dr ive, Suite 175
EcoSour ce
Waukesha, WI 53186
Revision 2
(800) 380-9640
Page 11