E93.1001EN.C Manual CD
+
29
Examples A (C63) and B (C33) maximum pipe lengths
Example B max. pipe length
water heater type
→
CD
+
80
CD
+
100
CD
+
120
CD
+
150
CD
+
180
Diameter air inlet
[mm]
80
100
100
130
130
Diameter flue outlet
[mm]
80
100
100
130
130
Concentric roof terminal [mm]
80/125
100/150
100/150
130/200
130/200
Maximum pipe length
[m]
(inlet + outlet together)
12,0
23,0
16,5
40,5
25,5
Part no. concentric roof terminal
E04.018.015
E04.018.001
E04.018.074
Part no. adaptor conc/twin:
E04.010.161
E04.018.033
Roof terminal Included
Example A max. pipe length
water heater type
→
CD
+
80
CD
+
100
CD
+
120
CD
+
150
CD
+
180
Diameter air inlet
[mm]
80
100
100
130
130
Diameter flue outlet
[mm]
80
100
100
130
130
Diam. roof terminals
[mm]
80
100
100
130
130
Maximum pipe length [m]
(inlet + outlet together)
18,0
31,5
24,0
44,5
30,0
Concentric roof terminal
Air inlet
Flue outlet
Example A
C63
Example B
C33
concentric/parallel adaptor