Operating screen:
W A T R H T R : b o i
l e r
o f f
> > > : 1 2 3 . 4 ° C ( 1 2 3 . 4 ° C )
Press [MENU]
Select "Parameter" using [◄] & [►] and press [ENTER]
Parameter menu:
I n s t a l l e r c o d e
0 0 0 0
Enter the 4-
digit code with the [◄] & [►] and the
[▲] & [▼] buttons and select [ENTER]
The code will blink a few seconds and when entered
correctly, the following parameters will be displayed.
NOTICE: These codes are user based and give access
to a selected amount of parameters, which
can be changed (Installer level 1/2).
Menu A: Heating
A 1
S t e p m o d u l
1
Function to activate the step modulation:
0 = Off
1 = On
Menu A: Heating
A 2
H E s
o f f 1 3
4
° C
CH supply temperature setting. This parameter
is the offset of the programmed CH temperature.
Menu A: Heating
A 3
H E s P r b 1 3
2 5
° C
Select the CH supply temperature control. This parameter
is the proportional range of the selected CH supply tempera-
ture.
Menu A: Heating
A 4
H E s c D i f 1 3
1 0
° C
Select the CH supply temperature control. This parameter
is the hysteresis of the selected CH supply temperature.
Menu A: Heating
A 5
H E s
l n t 1 3
6 0
S e c
Select the CH supply temperature control. This parameter
is the integration time of the selected CH supply temperature.
The screen texts on these
pages are standard part of
the software and apply to
CH systems (boilers)
and/or DHW devices (water
heaters).