E93.1001EN.C Manual CD
+
78
Menu B: Hot water
B C
D H d s c l n t 2 3
2 0 0 S e c
Function for the direct hot water boiler.
This parameter is the integration time of the selected HW
temperature of the boiler.
Menu B: Hot water
B D
D H d s c O f f 3
4
° C
Function for the cascaded direct hot water boilers.
This parameter is the offset of the selected HW temperature
of the cascaded boilers.
Menu B: Hot water
B E
D H d s c D i f 3
8
° C
Function for the cascaded direct hot water boilers.
This parameter is the hysteresis of the selected HW temper-
ature of the cascaded boilers.
Menu B: Hot water
B F
D H i s c D i f 4
5
° C
Function for the indirect hot water supply of the
boiler (tank).
This parameter is the hysteresis of the selected DHW tem-
perature of the calorifier/tank.
Menu B: Hot water
B G
D H i d e t g r a d
3
° C
Function for the indirect hot water supply of the
boiler (tank).
This parameter detects an (an accelerated) hot water de-
mand, when a larger (water) amount is being used.
Menu C: Cascade
C 1
M a x C a s c U n t
1 1
Function for the cascading of the boiler(s).
This parameter sets the total amount of cascaded boilers
(max. twelve boilers).
Menu C: Cascade
C 2
B u s
a d r e s s
0
Function for the cascading of the boiler(s).
This parameter determines the address of the boiler for the
total cascading control.
Master = 0, Slave 1 = 1 etc.
Menu C: Cascade
C 3
D H i c a s / m a s
0
Function for the cascading of the boiler(s).
This parameter determines if only the Master boiler or all boil-
ers of the cascade are used for indirect hot water.
0 = All
1 = Master
The screen texts on these
pages are standard part of
the software and apply to
CH systems (boilers)
and/or DHW devices (water
heaters).