E93.1001EN.C Manual CD
+
76
Menu A: Heating
A 6
H E
c O f f
3
4
° C
Select the cascaded boilers supply temperature control.
This parameter is the offset of the selected CH supply tem-
perature of EACH boiler of the total cascade.
Menu A: Heating
A 7
H E
c P r b
3
2 5
° C
Select the cascaded boilers supply temperature control.
This parameter is the proportional range of the selected CH
supply temperature of EACH boiler of the total cascade and of
the external (cascade) sensor.
Menu A: Heating
A 8
H E
c l n t
3
8 0
S e c
Select the cascaded boilers supply temperature control.
This parameter is the integration time of the selected CH sup-
ply temperature of EACH boiler of the total cascade and of
the external (cascade) sensor.
Menu A: Heating
A 9
T i m e r C o n t
0
Function to activate "external time controller":
0 = Off
1 = On
Connect to 13-14. Contact closed = daytime setting,
Contact open = night-time setting.
Menu B: Hot water
B 1
D H i p m p / t w v
1
Hot water function of the boiler by:
0 = pump
1 = 3-way valve
Menu B: Hot water
B 2
D H i f l o w L O
2 5
° C
Hot water function of the boiler. This parameter is the CH sup-
ply temperature LOW level with an indirect hot water demand.
Menu B: Hot water
B 3
D H i f l o w H I
8 5
° C
Hot water function of the boiler. This parameter is the CH sup-
ply temperature HIGH level with an indirect hot water de-
mand.
The screen texts on these
pages are standard part of
the software and apply to
CH systems (boilers)
and/or DHW devices (water
heaters).