Alarms and Messages of UA 410 L
80
Firmware V1.50 - Doku 2.0 06. April 2016
10.2.1 Transient alarms and messages
Transient alarms are one-time event alarms and are not time stamped for send time. As a result, transient
alarms are not deleted automatically after the event and must be cancelled manually. This applies regardless of
the setting made for
Selfholding
(Menu 6-2-3).
The following are transient alarms:
‐ Time-terminated defrosting
‐ Change of setpoint
‐ Electric power failure
‐ First start
10.2.2 Message log
A maximum of 25 alarms and messages with receive and send date and time are entered in the message log
and are stored in a ring buffer. When the ring buffer is full, the next new entry deletes the oldest entry.
Priority 0 alarms are only entered in the message log. Priority ”--” alarms are neither reported to the alarm server
nor entered in the message log.
Alarms may be lost by setting priority to 0 or ”--”. Priority and time delay apply only to High Tempera
ture and Low Temperature alarms. The global priority (Menu 6-1) applies to all other alarms.
Содержание UA 410 L Case Controller
Страница 30: ...Function of UA 410 L 24 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Страница 52: ...Installation and Startup of UA 410 L 46 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Страница 72: ...Operation of UA 410 L 66 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Страница 80: ...Menu Structure of UA 410 L 74 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Страница 82: ...Decommissioning and disposal 76 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Страница 92: ...Order numbers and accessories of UA 410 L 86 Firmware V1 50 Doku 2 0 06 April 2016 Notice...