Function of UA 410 L
23
Firmware V1.50 - Doku 2.0 06. April 2016
Before connecting to the case/coldroom controller, all BT 30 Temperature Displays must be addressed by
means of the exposed leads (see illustration):
Leads
Konfiguration BT 30
Address 1
Address 2
Address 3
Address 4
Green
Closed
Open
Closed
Closed
White
Closed
Closed
Open
Closed
Detailed information and connection instructions for the BT 30 can be found in the BT 30 operating
instruction.
Suppressing status display
The alarm symbol is displayed separately for low and high temperature alarm on each of the four sensors. To
suppress the alarm symbol, the setpoints for high and low temperature alarm must be adjusted to a value out
side the operating temperature range or the priorities must be adjusted to 0 or “--”.
If the Cooling symbol is to be suppressed in pure recording mode, the Cooling setpoint must be ad
justed to a value above the operating temperature.