Function of UA 410 L
22
Firmware V1.50 - Doku 2.0 06. April 2016
4.4
Temperature display BT 30
4.4.1
Offset for temperature display
An offset (parameter
Offset
in Menu 2) can be applied to temperature values as a means of compensating dif
ferences between readings on thermometers in the refrigerated display case and on the case controller.
This offset affects the complete functionality (cooling, defrosting, recording, etc.) for which the sen
sor is used.
4.4.2
Connecting BT 30 Temperature Display
Using a RJ45 distributor, one to four BT 30 Temperature Displays can be connected to the Temperature Data
Logging Controller at the DISPLAY terminals 1 to 6.
The "Cooling" and "Defrost" statuses are shown in BT 30 temperature displays as well as the temperature of the
sensor Rx.1 .. Rx.4. Alle angezeigten Werte beziehen sich allein auf den ausgewählten Fühler. In particular, no
cross-controller alarms are displayed.
UA 300 xC
green
w
h
ite
green
w
h
ite
green
w
h
ite
green
w
h
ite
Address 1
Address 2
Address 3
Address 4
R
J
45
switc
h
UA 300 xS
D
I
S
P
LA
Y
ZNR
.
51203
71
331
E2
D
I
N rai
l
mounting
P
ane
l
mounting
or
D
I
S
P
LA
Y
Controller type
Available temperature display on BT 30
Address 1
Address 2
Address 3
Address 4
UA 410 L
Rx.1
Rx.2
Rx.3
Rx.4
Содержание UA 410 L Case Controller
Страница 30: ...Function of UA 410 L 24 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Страница 52: ...Installation and Startup of UA 410 L 46 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Страница 72: ...Operation of UA 410 L 66 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Страница 80: ...Menu Structure of UA 410 L 74 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Страница 82: ...Decommissioning and disposal 76 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Страница 92: ...Order numbers and accessories of UA 410 L 86 Firmware V1 50 Doku 2 0 06 April 2016 Notice...